Model for determination of a power transmission system frequency response
Model for determination of a power transmission system frequency response, 2018., doktorska disertacija, Fakultet elektrotehnike i računarstva, Zagreb
CROSBI ID: 973020 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
Model for determination of a power transmission system frequency response
Autori
Levačić, Goran
Vrsta, podvrsta i kategorija rada
Ocjenski radovi, doktorska disertacija
Fakultet
Fakultet elektrotehnike i računarstva
Mjesto
Zagreb
Datum
28.09
Godina
2018
Stranica
281
Mentor
Uglešić, Ivo
Neposredni voditelj
Xemard, Alain
Ključne riječi
EMTP-RV, power transmission network, resonance phenomenon, resonant frequencies, frequency response, frequency dependent network equivalent, long cables, PSS/E, sensitive network areas, sensitivity analysis, Moriss’ Method
Sažetak
Traditional models of a power transmission networks are usually used only for performing a particular type of calculation. Gradual, but steady increase of electrical energy consumption, transit, as well as integration of new renewable energy sources require adjustment of the power system on the new circumstances. Similarly is with power system analysis and simulation software tools. In this Doctoral Thesis a custom mathematical model of three-phase transmission network for calculations in the frequency-domain in EMTP- type software is developed. With the possibility of analysis of resonant frequencies and power transmission network frequency response, it can be used as well for steady-state and time-domain calculations. Developed model in EMTP-RV is validated by comparison of load-flow results with the same model developed in planning and analysis tool PSS/E. Frequency dependent network equivalent seen from the certain point of the network can be very useful in cases of new power plant connection, because they can be transmitted by TSOs to power plant owners or manufacturers to perform certain type of calculations. Model of frequency dependent network equivalent is validated through comparison of time-domain results with full-network model and with on-site measurements. Furthermore, case scenario of power plant connection with long HVAC cable is analyzed on developed model to show its influence on network’s frequency response and resonant frequencies. Therefore, a procedure for identification of areas sensitive to the change of network topology is established. In order to determine the most influential parameters of the power transmission network on frequency response, a procedure for sensitivity analysis which consists of defining an input parameters and output signals and their parameterizing (linking) with EMTP-type module for parametric studies is established. Sensitivity analysis is performed graphically and using Moriss Method.