Pregled bibliografske jedinice broj: 962443
Influence of Load Peak Shaving on Battery System Capacity in an Islanded Building Microgrid
Influence of Load Peak Shaving on Battery System Capacity in an Islanded Building Microgrid // Proceedings of International Conference on Smart Systems and Technologies 2018 (SST2018) / Žagar, Drago ; Martinović, Goran ; Rimac-Drlje, Snježana ; Galić, Irena (ur.).
Osijek: Fakultet elektrotehnike, računarstva i informacijskih tehnologija Sveučilišta Josipa Jurja Strossmayera u Osijeku, 2018. str. 247-251 (predavanje, međunarodna recenzija, cjeloviti rad (in extenso), znanstveni)
CROSBI ID: 962443 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
Influence of Load Peak Shaving on Battery System Capacity in an Islanded Building Microgrid
Autori
Žnidarec, Matej ; Topić, Danijel ; Šljivac, Damir ; Klaić, Zvonimir ; Brandis, Andrej
Vrsta, podvrsta i kategorija rada
Radovi u zbornicima skupova, cjeloviti rad (in extenso), znanstveni
Izvornik
Proceedings of International Conference on Smart Systems and Technologies 2018 (SST2018)
/ Žagar, Drago ; Martinović, Goran ; Rimac-Drlje, Snježana ; Galić, Irena - Osijek : Fakultet elektrotehnike, računarstva i informacijskih tehnologija Sveučilišta Josipa Jurja Strossmayera u Osijeku, 2018, 247-251
ISBN
978-1-5386-7189-4
Skup
International Conference on Smart Systems and Technologies 2018 (SST 2018)
Mjesto i datum
Osijek, Hrvatska, 10.10.2018. - 12.10.2018
Vrsta sudjelovanja
Predavanje
Vrsta recenzije
Međunarodna recenzija
Ključne riječi
off-grid, islanded microgrid, battery system capacity, load peak shaving, demand side management
Sažetak
In this paper, building microgrid is modelled in the hardware in loop software Typhoon HIL. Microgrid consists of 30 kW wind turbine, 70 kWp photovoltaic system, building load and battery system. Energy management system is integrated into software model and simulations of the influence of the active load peak shaving technique on battery system capacity are conducted. In each case daily active power load peak is reduced by 1 % and battery system capacity is calculated. Every simulation is executed for the period of one week. Results show that battery system capacity is reducing with active power load peak shaving increase but not in a linear way like it is expected because of the properties of the microgrid model.
Izvorni jezik
Engleski
Znanstvena područja
Elektrotehnika
POVEZANOST RADA
Ustanove:
Fakultet elektrotehnike, računarstva i informacijskih tehnologija Osijek