Pretražite po imenu i prezimenu autora, mentora, urednika, prevoditelja

Napredna pretraga

Pregled bibliografske jedinice broj: 941895

Dose Calculation for Emergency Control Room HVAC Filter


Grgić, Davor; Vlahović, Štefica; Matijević, Mario; Dučkić, Paulina; Špalj, Srđan
Dose Calculation for Emergency Control Room HVAC Filter // 12th International Conference of the Croatian Nuclear Society Conference Proceedings / Vrbanić, Ivan ; Šadek, Siniša ; Bašić, Ivica (ur.).
Zagreb: Hrvatsko nuklearno društvo, 2018. str. S7173-1 (predavanje, međunarodna recenzija, cjeloviti rad (in extenso), znanstveni)


CROSBI ID: 941895 Za ispravke kontaktirajte CROSBI podršku putem web obrasca

Naslov
Dose Calculation for Emergency Control Room HVAC Filter

Autori
Grgić, Davor ; Vlahović, Štefica ; Matijević, Mario ; Dučkić, Paulina ; Špalj, Srđan

Vrsta, podvrsta i kategorija rada
Radovi u zbornicima skupova, cjeloviti rad (in extenso), znanstveni

Izvornik
12th International Conference of the Croatian Nuclear Society Conference Proceedings / Vrbanić, Ivan ; Šadek, Siniša ; Bašić, Ivica - Zagreb : Hrvatsko nuklearno društvo, 2018, S7173-1

ISBN
978-953-48100-0-2

Skup
12th International Conference of the Croatian Nuclear Society

Mjesto i datum
Zadar, Hrvatska, 03.06.2018. - 06.06.2018

Vrsta sudjelovanja
Predavanje

Vrsta recenzije
Međunarodna recenzija

Ključne riječi
Emergency Control Room, HVAC filter, gamma dose, point kernel, Monte Carlo

Sažetak
NPP Krsko is introducing Emergency Control Room (ECR) as part of safety upgrades. According to 10CFR50 Appendix A, GDC 19, both main control room and emergency control room should have adequate radiation protection to permit operators to shutdown the plant and keep it in safe shutdown conditions without receiving more than 50 mSv effective whole body dose, within 30 days from accident initiation. One of the important prerequisites to achieve that is proper operation of control room HVAC. In this work we are focused to calculation of gamma doses from radioactive materials accumulated in HEPA and charcoal filters during 30 days of HVAC operation. The dose at selected points around the filter was calculated using Microshield 10.0 point kernel code. The radioactive gamma source is calculated using RADTRAD 3.03 for plant’s severe accident SGTR sequence calculated with MAAP 4.0.7 code. Calculated dose rates at peak filter activity are compared against results obtained with SCALE 6.2 MAVRIC shielding sequence (Monaco Monte Carlo functional module and CADIS methodology). The reasonable agreement between point kernel and hybrid Monte Carlo results was obtained.

Izvorni jezik
Engleski



POVEZANOST RADA



Citiraj ovu publikaciju:

Grgić, Davor; Vlahović, Štefica; Matijević, Mario; Dučkić, Paulina; Špalj, Srđan
Dose Calculation for Emergency Control Room HVAC Filter // 12th International Conference of the Croatian Nuclear Society Conference Proceedings / Vrbanić, Ivan ; Šadek, Siniša ; Bašić, Ivica (ur.).
Zagreb: Hrvatsko nuklearno društvo, 2018. str. S7173-1 (predavanje, međunarodna recenzija, cjeloviti rad (in extenso), znanstveni)
Grgić, D., Vlahović, Š., Matijević, M., Dučkić, P. & Špalj, S. (2018) Dose Calculation for Emergency Control Room HVAC Filter. U: Vrbanić, I., Šadek, S. & Bašić, I. (ur.)12th International Conference of the Croatian Nuclear Society Conference Proceedings.
@article{article, author = {Grgi\'{c}, Davor and Vlahovi\'{c}, \v{S}tefica and Matijevi\'{c}, Mario and Du\v{c}ki\'{c}, Paulina and \v{S}palj, Sr\djan}, year = {2018}, pages = {S7173-1-S7173-14}, keywords = {Emergency Control Room, HVAC filter, gamma dose, point kernel, Monte Carlo}, isbn = {978-953-48100-0-2}, title = {Dose Calculation for Emergency Control Room HVAC Filter}, keyword = {Emergency Control Room, HVAC filter, gamma dose, point kernel, Monte Carlo}, publisher = {Hrvatsko nuklearno dru\v{s}tvo}, publisherplace = {Zadar, Hrvatska} }
@article{article, author = {Grgi\'{c}, Davor and Vlahovi\'{c}, \v{S}tefica and Matijevi\'{c}, Mario and Du\v{c}ki\'{c}, Paulina and \v{S}palj, Sr\djan}, year = {2018}, pages = {S7173-1-S7173-14}, keywords = {Emergency Control Room, HVAC filter, gamma dose, point kernel, Monte Carlo}, isbn = {978-953-48100-0-2}, title = {Dose Calculation for Emergency Control Room HVAC Filter}, keyword = {Emergency Control Room, HVAC filter, gamma dose, point kernel, Monte Carlo}, publisher = {Hrvatsko nuklearno dru\v{s}tvo}, publisherplace = {Zadar, Hrvatska} }