Pregled bibliografske jedinice broj: 941888
Fuel Handling Building Response to SFP Loss of Cooling
Fuel Handling Building Response to SFP Loss of Cooling // 12th International Conference of the Croatian Nuclear Society Conference Proceedings / Vrbanić, Ivan ; Šadek, Siniša ; Bašić, Ivica (ur.).
Zagreb: Hrvatsko nuklearno društvo, 2018. str. S5-174-1-S5-174-1 (predavanje, međunarodna recenzija, sažetak, znanstveni)
CROSBI ID: 941888 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
Fuel Handling Building Response to SFP Loss of Cooling
Autori
Grgić, Davor ; Fancev, Tomislav ; Šadek, Siniša ; Špalj, Srđan
Vrsta, podvrsta i kategorija rada
Sažeci sa skupova, sažetak, znanstveni
Izvornik
12th International Conference of the Croatian Nuclear Society Conference Proceedings
/ Vrbanić, Ivan ; Šadek, Siniša ; Bašić, Ivica - Zagreb : Hrvatsko nuklearno društvo, 2018, S5-174-1-S5-174-1
ISBN
978-953-48100-0-2
Skup
12th International Conference of the Croatian Nuclear Society
Mjesto i datum
Zadar, Hrvatska, 03.06.2018. - 06.06.2018
Vrsta sudjelovanja
Predavanje
Vrsta recenzije
Međunarodna recenzija
Ključne riječi
FHB, SFP heat-up, GOTHIC, equipment qualification
Sažetak
GOTHIC model of Fuel Handling Building (FHB) was developed for NPP Krsko. Simplified model of Spent Fuel Pool (SFP) is part of FHB model. SFP model includes control volumes with racks, transfer channel, and cask loading area. It is possible to plug more detailed SFP model (takes into account details of coolant natural circulation) into the same FHB model too, but that has negative influence on duration of calculation. SFP heat-up can be modeled with heaters having time-dependent forcing function to simulate decay heat, or heat source can be placed directly in fuel heat structure. In order to model response of FHB to loss of SFP cooling, up to the point when water level drops to top of active fuel, it is usually enough to use heater as a representation of decay heat. That way it is possible to calculate loss of water from the pool by evaporation and heat-up of FHB atmosphere. The temperature, pressure, and relative humidity are calculated in FHB rooms without and with depressurization panel that will be introduced as a part of plant’s safety upgrade project. Calculated thermal-hydraulic conditions in FHB rooms can be used in establishing environmental conditions for equipment qualification in the frame of equipment survivability program.
Izvorni jezik
Engleski
POVEZANOST RADA
Ustanove:
Fakultet elektrotehnike i računarstva, Zagreb