Pregled bibliografske jedinice broj: 938117
Study of Operative Temperature Using the Novel Detail Approach in Determining Mean Radiant Temperature – Comparison Between Wall-Mounted Convector and Conventional Radiator
Study of Operative Temperature Using the Novel Detail Approach in Determining Mean Radiant Temperature – Comparison Between Wall-Mounted Convector and Conventional Radiator // Transactions of FAMENA, 42 (2018), SI-1; 27-38 doi:10.21278/TOF.42Si103 (međunarodna recenzija, članak, znanstveni)
CROSBI ID: 938117 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
Study of Operative Temperature Using the Novel Detail Approach in Determining Mean Radiant Temperature – Comparison Between Wall-Mounted Convector and Conventional Radiator
Autori
Tomorad, Jura ; Horvat, Ivan ; Dović, Damir
Izvornik
Transactions of FAMENA (1333-1124) 42
(2018), SI-1;
27-38
Vrsta, podvrsta i kategorija rada
Radovi u časopisima, članak, znanstveni
Ključne riječi
Mean radiant temperature ; operative temperature ; thermal comfort ; thermography ; heat emitters
Sažetak
Most of the physical parameters that are used to assess the satisfaction with the ambient thermal condition in a mathematical way are contained within the definition of operative temperature. This temperature, which can be used as a representative of indoor thermal comfort, is a function of the air temperature, the mean radiant temperature and the relative air velocity. In this paper, the room air, mean radian temperature and indoor air velocity were determined experimentally for wall-mounted convector and conventional radiator at controlled room conditions. The room air temperature and indoor air velocity were continuously measured at several positions and heights (0.75 m and 1.5 m) using calibrated T- type thermocouples and hot wire probes, while mean radiant temperature was calculated using the thermograms captured by the IR thermal camera and numerically computed radiation view factors. Each wall was divided into several sections with approximately similar temperatures (differences < 0.5 °C) for which view factors were determined. Thermal heat output of the tested heat emitters was derived according to EN 442-2:2014. Obtained results were analysed and conclusions about the achieved thermal comfort and related energy saving were made accordingly.
Izvorni jezik
Engleski