Lightning caused overvoltages on power transformers recorded by on-line transient overvoltage monitoring system


Keitoue, Samir; Murat, Ivan; Filipović-Grčić, Božidar; Župan, Alan; Damjanović, Ivana; Pavić, Ivica
Lightning caused overvoltages on power transformers recorded by on-line transient overvoltage monitoring system // SECOND SEERC CONFERENCE 2018: ENERGY TRANSITION AND INNOVATIONS IN ELECTRICITY SECTOR
Kijev, 2018. str. 1-10 (predavanje, međunarodna recenzija, cjeloviti rad (in extenso), znanstveni)


CROSBI ID: 937166 Za ispravke kontaktirajte CROSBI podršku putem web obrasca

Naslov
Lightning caused overvoltages on power transformers recorded by on-line transient overvoltage monitoring system

Autori
Keitoue, Samir ; Murat, Ivan ; Filipović-Grčić, Božidar ; Župan, Alan ; Damjanović, Ivana ; Pavić, Ivica

Vrsta, podvrsta i kategorija rada
Radovi u zbornicima skupova, cjeloviti rad (in extenso), znanstveni

Izvornik
SECOND SEERC CONFERENCE 2018: ENERGY TRANSITION AND INNOVATIONS IN ELECTRICITY SECTOR / - Kijev, 2018, 1-10

Skup
2nd South East European Regional CIGRE Conference 2018: Energy Transition and Innovations in Electricity Sector

Mjesto i datum
Kijev, Ukrajina, 12.06.2018. - 13.06.2018

Vrsta sudjelovanja
Predavanje

Vrsta recenzije
Međunarodna recenzija

Ključne riječi
On-line transient overvoltage monitoring system ; power transformers ; lightning overvoltages ; lightning location system

Sažetak
Transient overvoltages generated by lightning strikes or switching operations represent a significant risk to bushings and windings of power transformers. They cause stress on the insulation system and can, over time, cause dielectric failure and damage to power transformers. Many transformer failures are reported as dielectric failures and they are not necessarily linked to any particular event when they occur but may be the result of prior damage from transient overvoltage events. Lightning and switching overvoltage waveforms appearing at transformer terminals in real operating conditions may significantly differ from standard impulse voltage waveforms used during laboratory testing. The number and amplitudes of overvoltages which stress the insulation depend on various parameters such as the lightning strike density in the considered area, since it determines how often the transformer is stressed by lightning overvoltages. Since the overvoltage amplitudes at transformer terminals are usually unknown, an on-line overvoltage transient recorder can be used with the ability to sample, analyse and store transients in real-time. In this paper, an on-line transient overvoltage monitoring system (TOMS) for power transformers is presented that is capable to continuously record in real-time various kinds of transient overvoltages such as lightning or switching overvoltages. Special attention is paid to lightning caused transient overvoltages recorded at the terminals of 150 MVA power transformer. Recorded waveforms originating from lightning strikes to overhead lines are correlated with data from the lightning location system (LLS) and supervisory control and data acquisition (SCADA) system. Collected data about overvoltage stresses can be used as the basis for the assessment of the transformer insulation condition, estimation of health index and for analysis of various kinds of events such as faults or equipment failures.

Izvorni jezik
Engleski

Znanstvena područja
Elektrotehnika



POVEZANOST RADA


Projekti:
HRZZ-IP-2013-11-9299 - Razvoj naprednih visokonaponskih sustava primjenom novih informacijskih i komunikacijskih tehnologija (DAHVAT) (Uglešić, Ivo, HRZZ ) ( CroRIS)

Ustanove:
KONČAR - Institut za elektrotehniku d.d.,
Fakultet elektrotehnike i računarstva, Zagreb

Poveznice na cjeloviti tekst rada:

Pristup cjelovitom tekstu rada

Citiraj ovu publikaciju:

Keitoue, Samir; Murat, Ivan; Filipović-Grčić, Božidar; Župan, Alan; Damjanović, Ivana; Pavić, Ivica
Lightning caused overvoltages on power transformers recorded by on-line transient overvoltage monitoring system // SECOND SEERC CONFERENCE 2018: ENERGY TRANSITION AND INNOVATIONS IN ELECTRICITY SECTOR
Kijev, 2018. str. 1-10 (predavanje, međunarodna recenzija, cjeloviti rad (in extenso), znanstveni)
Keitoue, S., Murat, I., Filipović-Grčić, B., Župan, A., Damjanović, I. & Pavić, I. (2018) Lightning caused overvoltages on power transformers recorded by on-line transient overvoltage monitoring system. U: SECOND SEERC CONFERENCE 2018: ENERGY TRANSITION AND INNOVATIONS IN ELECTRICITY SECTOR.
@article{article, author = {Keitoue, Samir and Murat, Ivan and Filipovi\'{c}-Gr\v{c}i\'{c}, Bo\v{z}idar and \v{Z}upan, Alan and Damjanovi\'{c}, Ivana and Pavi\'{c}, Ivica}, year = {2018}, pages = {1-10}, keywords = {On-line transient overvoltage monitoring system, power transformers, lightning overvoltages, lightning location system}, title = {Lightning caused overvoltages on power transformers recorded by on-line transient overvoltage monitoring system}, keyword = {On-line transient overvoltage monitoring system, power transformers, lightning overvoltages, lightning location system}, publisherplace = {Kijev, Ukrajina} }
@article{article, author = {Keitoue, Samir and Murat, Ivan and Filipovi\'{c}-Gr\v{c}i\'{c}, Bo\v{z}idar and \v{Z}upan, Alan and Damjanovi\'{c}, Ivana and Pavi\'{c}, Ivica}, year = {2018}, pages = {1-10}, keywords = {On-line transient overvoltage monitoring system, power transformers, lightning overvoltages, lightning location system}, title = {Lightning caused overvoltages on power transformers recorded by on-line transient overvoltage monitoring system}, keyword = {On-line transient overvoltage monitoring system, power transformers, lightning overvoltages, lightning location system}, publisherplace = {Kijev, Ukrajina} }




Contrast
Increase Font
Decrease Font
Dyslexic Font