Pregled bibliografske jedinice broj: 905646
Carbon monoxide and carbon dioxide in closed-type power transformers
Carbon monoxide and carbon dioxide in closed-type power transformers // Energija = Journal of Energy, 61 (2012), Special Issue; 28-34 (međunarodna recenzija, članak, stručni)
CROSBI ID: 905646 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
Carbon monoxide and carbon dioxide in closed-type power transformers
Autori
Hadži-Skerlev, Anđela ; Vrsaljko, Dijana ; Haramija, Veronika ; Musulin, Božena
Izvornik
Energija = Journal of Energy (0013-7448) 61
(2012), Special Issue;
28-34
Vrsta, podvrsta i kategorija rada
Radovi u časopisima, članak, stručni
Ključne riječi
carbon monoxide ; carbon dioxide ; cellulose ; mineral oil
Sažetak
Gases carbon monoxide (CO) and carbon dioxide (CO2) are formed in transformers in larger quantities as a product of degradation of cellulose, than by oxidation of oil. In transformers with closed-type breathing system, without any indication of failure or fault, it was observed that the concentrations of CO are higher than the typical values according to IEC 60599 and CO2/CO ratios lower than 3 frequently have been found. This paper presents results of laboratory investigation of some influence parameters on formation gases CO and CO2. The typical values for CO as well scheme concerning their ratios need to be revised in standard IEC 60599. The criteria need to be established separately for closed type transformers.
Izvorni jezik
Engleski
Znanstvena područja
Elektrotehnika
POVEZANOST RADA
Ustanove:
KONČAR - Institut za elektrotehniku d.d.