Pregled bibliografske jedinice broj: 905628
Research of transformer main insulation design rules
Research of transformer main insulation design rules // Energija = Journal of Energy, 61 (2012), Special Issue; 13-19 (međunarodna recenzija, članak, stručni)
CROSBI ID: 905628 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
Research of transformer main insulation design rules
Autori
Gabrić, Petar ; Mikulecky, Antun ; Glavinić, Maja ; Podobnik, Vladimir
Izvornik
Energija = Journal of Energy (0013-7448) 61
(2012), Special Issue;
13-19
Vrsta, podvrsta i kategorija rada
Radovi u časopisima, članak, stručni
Ključne riječi
power transformer ; insulation ; electric field ; partial discharges ; insulation design
Sažetak
Kappeler research performed more than 50 years ago is widely used for HV transformers insulation design. Even though the original experiment was done for oil ducts width from 0.5 to 6 mm, the results have been extrapolated to ducts up to 100 and more mm without detailed publication that would confirm the validity of this extrapolation. This paper presents the experiment that aims to expand Kappeler research to oil duct width up to 30 mm. Model setup also allows creepage and barriers effect testing up to 30 mm.
Izvorni jezik
Engleski
Znanstvena područja
Elektrotehnika
POVEZANOST RADA
Ustanove:
KONČAR - Institut za elektrotehniku d.d.