Pregled bibliografske jedinice broj: 874800
Monitoring of transient overvoltages on the power transformers and shunt reactors – field experience in the Croatian power transmission system
Monitoring of transient overvoltages on the power transformers and shunt reactors – field experience in the Croatian power transmission system // 4th International Colloquium "Transformer Research and Asset Management", Pula, Croatia, May 10 – 12, 2017
Zagreb: CIGRÉ, 2017. str. 1-15 (predavanje, međunarodna recenzija, cjeloviti rad (in extenso), znanstveni)
CROSBI ID: 874800 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
Monitoring of transient overvoltages on the power transformers and shunt reactors – field experience in the Croatian power transmission system
Autori
Filipović-Grčić, Božidar ; Franc, Bojan ; Uglešić, Ivo ; Pavić, Ivica ; Keitoue Samir ; Murat, Ivan ; Ivanković, Igor
Vrsta, podvrsta i kategorija rada
Radovi u zbornicima skupova, cjeloviti rad (in extenso), znanstveni
Izvornik
4th International Colloquium "Transformer Research and Asset Management", Pula, Croatia, May 10 – 12, 2017
/ - Zagreb : CIGRÉ, 2017, 1-15
Skup
4th International Colloquium "Transformer Research and Asset Management"
Mjesto i datum
Pula, Hrvatska, 10.05.2017. - 12.05.2017
Vrsta sudjelovanja
Predavanje
Vrsta recenzije
Međunarodna recenzija
Ključne riječi
Transient overvoltage monitoring system ; lightning location system ; lightning and switching overvoltages ; power transformers ; shunt reactors ; EMTP-RV
Sažetak
Power transformers and shunt reactors may be subjected to various dielectric stresses such as lightning and switching overvoltages. Since the exposure of equipment to overvoltages during operation and the overvoltage amplitudes are usually unknow, an on-line overvoltage transient recorder is used with the ability to sample, analyze and store transients at transformer terminals in real-time. In this paper, transient overvoltage monitoring system is presented. Overvoltages are measured on the outside measurement terminal of the shunt reactor and transformer bushing. Field experience regarding the application of monitoring system in Croatia is described including different cases of lightning and switching overvoltages. Lightning overvoltages recorded by monitoring system are correlated with data from the lightning location system (LLS). Switching overvoltages recorded on the shunt reactor are compared with numerical simulations in EMTP-RV software. Collected data about overvoltage stresses can be used as the basis for the assessment of the transformer and shunt reactor insulation condition and estimation of health index.
Izvorni jezik
Engleski
Znanstvena područja
Elektrotehnika
Napomena
Paper TLM-05
POVEZANOST RADA
Projekti:
HRZZ-IP-2013-11-9299 - Razvoj naprednih visokonaponskih sustava primjenom novih informacijskih i komunikacijskih tehnologija (DAHVAT) (Uglešić, Ivo, HRZZ ) ( CroRIS)
Ustanove:
KONČAR - Institut za elektrotehniku d.d.,
Fakultet elektrotehnike i računarstva, Zagreb
Profili:
Božidar Filipović-Grčić
(autor)
Ivica Pavić
(autor)
Bojan Franc
(autor)
Igor Ivanković
(autor)
Ivan Murat
(autor)
Ivo Uglešić
(autor)
Samir Keitoue
(autor)