Pretražite po imenu i prezimenu autora, mentora, urednika, prevoditelja

Napredna pretraga

Pregled bibliografske jedinice broj: 864307

Transformer insulation coordination using volt– time curve and limit–state surface formulation


Sarajčev, Petar; Jakus, Damir; Jolevski, Danijel
Transformer insulation coordination using volt– time curve and limit–state surface formulation // International journal of electrical power & energy systems, 90 (2017), 256-266 doi:10.1016/j.ijepes.2017.02.016 (međunarodna recenzija, članak, znanstveni)


CROSBI ID: 864307 Za ispravke kontaktirajte CROSBI podršku putem web obrasca

Naslov
Transformer insulation coordination using volt– time curve and limit–state surface formulation

Autori
Sarajčev, Petar ; Jakus, Damir ; Jolevski, Danijel

Izvornik
International journal of electrical power & energy systems (0142-0615) 90 (2017); 256-266

Vrsta, podvrsta i kategorija rada
Radovi u časopisima, članak, znanstveni

Ključne riječi
Insulation coordination ; Limit–state surface ; Lightning ; EMTP–ATP ; Systematic simulations ; Volt–time curve

Sažetak
This paper presents a novel method for the power transformer insulation coordination, based on the risk of failure analysis due to lightning surges, that uses its insulation strength volt– time curve and a limit–state surface formulation. The limit–state surface is derived in a novel way, from the optimal number of systematic numerical simulations of transformer terminal overvoltages—emanating from station impinging lightning surges—while accounting for the transformer insulation volt–time curve and surge arresters protective characteristics and disposition. The proposed method further employs a state-of-the-art transmission line (TL) and substation equipment models for lightning-surge transient analysis, constructed in the EMTP software package. It also uses the electrogeometric model of lightning attachment to TLs, in order to estimate the expected number of direct lightning strikes, along with a bivariate statistical distribution of lightning currents. The main aspects of the proposed method are demonstrated by means of the computational example featuring an air-insulated substation power transformer lightning insulation coordination. Simulation results exhibit many benefits of the proposed method. Sensitivity analysis further reveals different influences that the various model parameters have on the transformer insulation coordination design.

Izvorni jezik
Engleski

Znanstvena područja
Elektrotehnika



POVEZANOST RADA


Ustanove:
Fakultet elektrotehnike, strojarstva i brodogradnje, Split

Profili:

Avatar Url Petar Sarajčev (autor)

Avatar Url Damir Jakus (autor)

Avatar Url Danijel Jolevski (autor)

Poveznice na cjeloviti tekst rada:

doi www.sciencedirect.com dx.doi.org

Citiraj ovu publikaciju:

Sarajčev, Petar; Jakus, Damir; Jolevski, Danijel
Transformer insulation coordination using volt– time curve and limit–state surface formulation // International journal of electrical power & energy systems, 90 (2017), 256-266 doi:10.1016/j.ijepes.2017.02.016 (međunarodna recenzija, članak, znanstveni)
Sarajčev, P., Jakus, D. & Jolevski, D. (2017) Transformer insulation coordination using volt– time curve and limit–state surface formulation. International journal of electrical power & energy systems, 90, 256-266 doi:10.1016/j.ijepes.2017.02.016.
@article{article, author = {Saraj\v{c}ev, Petar and Jakus, Damir and Jolevski, Danijel}, year = {2017}, pages = {256-266}, DOI = {10.1016/j.ijepes.2017.02.016}, keywords = {Insulation coordination, Limit–state surface, Lightning, EMTP–ATP, Systematic simulations, Volt–time curve}, journal = {International journal of electrical power and energy systems}, doi = {10.1016/j.ijepes.2017.02.016}, volume = {90}, issn = {0142-0615}, title = {Transformer insulation coordination using volt– time curve and limit–state surface formulation}, keyword = {Insulation coordination, Limit–state surface, Lightning, EMTP–ATP, Systematic simulations, Volt–time curve} }
@article{article, author = {Saraj\v{c}ev, Petar and Jakus, Damir and Jolevski, Danijel}, year = {2017}, pages = {256-266}, DOI = {10.1016/j.ijepes.2017.02.016}, keywords = {Insulation coordination, Limit–state surface, Lightning, EMTP–ATP, Systematic simulations, Volt–time curve}, journal = {International journal of electrical power and energy systems}, doi = {10.1016/j.ijepes.2017.02.016}, volume = {90}, issn = {0142-0615}, title = {Transformer insulation coordination using volt– time curve and limit–state surface formulation}, keyword = {Insulation coordination, Limit–state surface, Lightning, EMTP–ATP, Systematic simulations, Volt–time curve} }

Časopis indeksira:


  • Current Contents Connect (CCC)
  • Web of Science Core Collection (WoSCC)
    • Science Citation Index Expanded (SCI-EXP)
    • SCI-EXP, SSCI i/ili A&HCI
  • Scopus


Citati:





    Contrast
    Increase Font
    Decrease Font
    Dyslexic Font