RELAP5/mod2 Analysis of Inadvertent Closing of the Main Steam Isolation Valve in NPP Krško
RELAP5/mod2 Analysis of Inadvertent Closing of the Main Steam Isolation Valve in NPP Krško // Nuclear Option in Countries with Small and Medium Electricity Grid / Knapp, Vladimir ; Čavlina, Nikola (ur.).
Opatija, Hrvatska: Hrvatsko nuklearno društvo, 1996. str. 447-455 (poster, nije recenziran, cjeloviti rad (in extenso), znanstveni)
CROSBI ID: 8415 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
RELAP5/mod2 Analysis of Inadvertent Closing of the Main Steam Isolation Valve in NPP Krško
Autori
Čavlina, Nikola ; Debrecin, Nenad ; Grgić, Davor ; Aralica, Marin
Vrsta, podvrsta i kategorija rada
Radovi u zbornicima skupova, cjeloviti rad (in extenso), znanstveni
Izvornik
Nuclear Option in Countries with Small and Medium Electricity Grid
/ Knapp, Vladimir ; Čavlina, Nikola - : Hrvatsko nuklearno društvo, 1996, 447-455
Skup
International Conference: Nuclear Option in Countries with Small and Medium Electricity Grid
Mjesto i datum
Opatija, Hrvatska, 07.10.1996. - 09.10.1996
Vrsta sudjelovanja
Poster
Vrsta recenzije
Nije recenziran
Ključne riječi
NPP safety; transient analyses; MSIV closure
Sažetak
The paper describes the use of system code RELAP5/mod2 in analysis of inadvertent closing of the main
steam isolation valve that happened in NPP Krško on September, 25 1995. Three cases were calculated in order to
address different aspects of the modelled transient. This preliminary calculation shows that, even though the real
plant behaviour isnt completely reproduced, such kind of analysis can help to better understand plant
behaviour and to identify important phenomena in the plant during transient. The result of the calculation for the case
no. 3, indicates that, with better understanding of status of the plant systems, calculated results could be very similar
to the plant data.