Estimating BFOR on HV Transmission Lines Using EMTP and Curve of Limiting Parameters
Estimating BFOR on HV Transmission Lines Using EMTP and Curve of Limiting Parameters // Proceedings of the International Conference on Power Systems Transients (IPST2015) / Uglesic, I. ; Ametani, A. ; Correia de Barros, M. T. (ur.).
Cavtat, Hrvatska, 2015. (predavanje, međunarodna recenzija, cjeloviti rad (in extenso), znanstveni)
CROSBI ID: 766949 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
Estimating BFOR on HV Transmission Lines Using EMTP and Curve of Limiting Parameters
Autori
Sarajcev, Petar ; Vasilj, Josip ; Sereci, Patrik
Vrsta, podvrsta i kategorija rada
Radovi u zbornicima skupova, cjeloviti rad (in extenso), znanstveni
Izvornik
Proceedings of the International Conference on Power Systems Transients (IPST2015)
/ Uglesic, I. ; Ametani, A. ; Correia de Barros, M. T. - , 2015
Skup
International Conference on Power Systems Transients (IPST2015)
Mjesto i datum
Cavtat, Hrvatska, 15.06.2015. - 18.06.2015
Vrsta sudjelovanja
Predavanje
Vrsta recenzije
Međunarodna recenzija
Ključne riječi
Backflashover; Bivariate statistical distribution; BFOR; EGM; EMTP; Lightning; Transmission line
Sažetak
This paper presents a method for estimating the backflashover rate (BFOR) on high voltage (HV) transmission lines. The proposed method employs a state-of-the-art model of HV transmission line (TL) for backflashover analysis, assembled within the EMTP-ATP program―with EMTP running in batch mode―to construct the curve of limiting parameters (CLP). The probability of backflashover occurrence at a particular TL tower is obtained by computing the volume under the surface of the probability density function of the bivariate log-normal statistical distribution (of lightning current parameters), bounded by the CLP in the coordinate system of lightning-current amplitude and wave-front duration. This probability, in combination with the estimated number of direct lightning strikes to TL towers, obtained from the application of the electrogeometric model, provides the associated BFOR, assuming it is further normalized on the basis of 100 km-years. The usage of the proposed method is demonstrated on a typical HV transmission line. A sensitivity study for estimating the BFOR with the proposed method is provided as well.