ULTRASONIC METHOD FOR TESTING OF POWER TRANSFORMERS
ULTRASONIC METHOD FOR TESTING OF POWER TRANSFORMERS // Proceedings of the 3rd International Colloquium Transformer Research and Asset Management, Split, Croatia, October 15 – 17, 2014
Split, Hrvatska, 2014. (predavanje, međunarodna recenzija, cjeloviti rad (in extenso), znanstveni)
CROSBI ID: 750724 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
ULTRASONIC METHOD FOR TESTING OF POWER TRANSFORMERS
Autori
Brezak, Danijel ; Filipović-Grčić, Dalibor
Vrsta, podvrsta i kategorija rada
Radovi u zbornicima skupova, cjeloviti rad (in extenso), znanstveni
Izvornik
Proceedings of the 3rd International Colloquium Transformer Research and Asset Management, Split, Croatia, October 15 – 17, 2014
/ - , 2014
Skup
3rd International Colloquium Transformer Research and Asset Management, Split, Croatia, October 15 – 17, 2014
Mjesto i datum
Split, Hrvatska, 15.10.2014. - 17.10.2014
Vrsta sudjelovanja
Predavanje
Vrsta recenzije
Međunarodna recenzija
Ključne riječi
diagnostics; power transformer; partial discharges; ultrasound; acoustic emission
Sažetak
Ultrasonic method of detecting PD is based on the fact that the electrical energy of the PD transforms in a mechanical energy, an ultrasonic acoustic wave that spreads through the transformer to the tank wall. From time difference of wave detection on different sensors, a possible location of the source can be estimated. Ultrasonic method can detect other transformer deficiencies such as loose contacts and local overheating of oil (T>200°C). Three case studies are given in this paper. The first case was where DGA indicates the thermal problem in the oil and the result of ultrasonic testing points at OLTC contacts. In the second case an ultrasonic method was performed after electrical method detected high levels of PD at voltages much lower than the nominal. Ultrasonic method detected non-grounded parts of the returning limb electrostatic screen. In the third case, a failure of transformer, namely a breakdown from the HV bushing end shield, initiated a series of tests on similar transformers installed at the same substation. The assumption was that PD occurred in the shied epoxy insulation and eventually caused the breakdown.
Izvorni jezik
Engleski