Pregled bibliografske jedinice broj: 742037
Rationalization of cooling water consumption in extraction system B-811 LSV
Rationalization of cooling water consumption in extraction system B-811 LSV // Croatian journal of food science and technology, 6 (2014), 2; 124-130 (recenziran, članak, stručni)
CROSBI ID: 742037 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
Rationalization of cooling water consumption in extraction system B-811 LSV
Autori
Budžaki, Sandra ; Čačić, Frane ; Miljić, Goran
Izvornik
Croatian journal of food science and technology (1847-3466) 6
(2014), 2;
124-130
Vrsta, podvrsta i kategorija rada
Radovi u časopisima, članak, stručni
Ključne riječi
rationalization ; cooling water ; extraction ; cooling tower
Sažetak
Water (drinkable) is vital natural resource, and during the last few decades it is imperative to reduce its needless consumption. Extraction devices are known for their significant cooling water consumption and laboratory scale devices mainly use drinkable water. Aim of this paper was rationalization of cooling water consumption during extractions in universal extraction system B-811 LSV by recirculating cooling water trough cooling tower.In order to obtain the data for cooling tower design, measurements of cooling water flow, inlet and outlet cooling water temperatures, air humidity and temperature were conducted. Design of cooling tower based on obtained values resulted in cylindrical cooling tower, 81.45 cm height and with base radius of 13.96 cm.Cooling water consumption was reduced 56.87 %.
Izvorni jezik
Engleski
Znanstvena područja
Prehrambena tehnologija
POVEZANOST RADA
Ustanove:
Prehrambeno-tehnološki fakultet, Osijek
Poveznice na cjeloviti tekst rada:
hrcak.srce.hr www.ptfos.unios.hr hrcak.srce.hr www.ptfos.unios.hrCitiraj ovu publikaciju:
Uključenost u ostale bibliografske baze podataka::
- CAB Abstracts
- FSTA: Food Science and Technology Abstracts