Pregled bibliografske jedinice broj: 700292
Optimization of OPDT Protection for Overcooling Accidents
Optimization of OPDT Protection for Overcooling Accidents // Proceedings of the 10th International Conference on Nuclear Option in Countries with Small and Medium Electricity Grids / Čavlina, Nikola ; Grgić, Davor ; Pevec, Dubravko (ur.).
Zagreb: Hrvatsko nuklearno društvo, 2014. str. 153-1 (poster, međunarodna recenzija, cjeloviti rad (in extenso), znanstveni)
CROSBI ID: 700292 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
Optimization of OPDT Protection for Overcooling Accidents
Autori
Benčik, Vesna ; Grgić, Davor ; Šadek, Siniša ; Čavlina , Nikola
Vrsta, podvrsta i kategorija rada
Radovi u zbornicima skupova, cjeloviti rad (in extenso), znanstveni
Izvornik
Proceedings of the 10th International Conference on Nuclear Option in Countries with Small and Medium Electricity Grids
/ Čavlina, Nikola ; Grgić, Davor ; Pevec, Dubravko - Zagreb : Hrvatsko nuklearno društvo, 2014, 153-1
ISBN
978-953-55224-6-1
Skup
10th International Conference on Nuclear Option in Countries with Small and Medium Electricity Grids
Mjesto i datum
Zadar, Hrvatska, 01.06.2014. - 04.06.2014
Vrsta sudjelovanja
Poster
Vrsta recenzije
Međunarodna recenzija
Ključne riječi
OPDT protection; decrease of feed water temperature; steam line break
Sažetak
Overcooling accidents are typically resulting in power increase due to negative moderator feedback. There are more protection set points resp onsible for terminating power increase. OPDT protection set point is typically protection from exceeding fuel centre line temperature due to reactivity and power increase. It is important to actuate reactor trip signal early enough, but to be able to filte r out events where actuation is not necessary. Different concepts of coolant temperature compensation as part of OPDT set point protection were studied for decrease of feedwater temperature accident and for small main steam line breaks from full power for NPP Krško. Computer code RELAP5/mod 3.3 was used in calculation. The influence of different assumptions in accident description as well as nuclear core characteristics were described.
Izvorni jezik
Engleski
Znanstvena područja
Elektrotehnika
POVEZANOST RADA
Projekti:
036-0361590-1589 - Nuklearne elektrane za održivu proizvodnju električne energije (Feretić, Danilo, MZO ) ( CroRIS)
Ustanove:
Fakultet elektrotehnike i računarstva, Zagreb