Pretražite po imenu i prezimenu autora, mentora, urednika, prevoditelja

Napredna pretraga

Pregled bibliografske jedinice broj: 599193

CIGRÉ Technical Brochure No. 513: Final Report of the 2004 – 2007 International Enquiry on Reliability of High Voltage Equipment, Part 5 - Gas Insulated Switchgear (GIS)


Carvalho A.; Cormenzana M. L.; Furuta, H.; Grieshaber, W.; Hyrczak A.; Kopejtkova D.; Krone, J. G.; Kudoke, M.; Makareinis D.; Martins, J. F. et al.
CIGRÉ Technical Brochure No. 513: Final Report of the 2004 – 2007 International Enquiry on Reliability of High Voltage Equipment, Part 5 - Gas Insulated Switchgear (GIS). Pariz: CIGRÉ, 2012 (ostalo)


CROSBI ID: 599193 Za ispravke kontaktirajte CROSBI podršku putem web obrasca

Naslov
CIGRÉ Technical Brochure No. 513: Final Report of the 2004 – 2007 International Enquiry on Reliability of High Voltage Equipment, Part 5 - Gas Insulated Switchgear (GIS)

Autori
Carvalho A. ; Cormenzana M. L. ; Furuta, H. ; Grieshaber, W. ; Hyrczak A. ; Kopejtkova D. ; Krone, J. G. ; Kudoke, M. ; Makareinis D. ; Martins, J. F. ; Meštrović, Krešimir ; Ohno I. ; Östlund, J. ; Park, K.-Y. ; Patel, J. ; Protze, C. ; Runde, M. ; Schmid, J. ; Skog, J. E. ; Sölver, C. E. ; Sweeney, B. ; Waite, F.

Vrsta, podvrsta i kategorija knjige
Autorske knjige, ostalo, strucna

Izdavač
CIGRÉ

Grad
Pariz

Godina
2012

Stranica
172

ISBN
978-2-85873-206-7

Ključne riječi
high voltage equipment; reliability; maintenance; enquiry; gas insulated switchgear; major failures; minor failures; major failure frequencies; failure characteristics

Sažetak
The 1st GIS international survey questionnaire was circulated in 1991 and both users and manufacturers were addressed. It collected experience up to 31.12.1990. 109 users from 34 countries and 18 manufacturers from 9 countries responded to the questionnaire. The user’s experience represented 1 817 GIS, 10 531 circuit breaker-bays (CB-bays) and 78 036 CBbay-years, the manufacturer’s experience represented 4 867 GIS, 24 870 CB-bays and 199 473 CB-bay-years. The questionnaire addressed: general data about GIS installations, factors which contributed to selection of GIS over AIS, adequacy of existing design/production/site test procedures, reliability, availability and maintainability, cause of major failures, future trends/condition monitoring /diagnostics and general open-ended questions. The survey and data analysis were published in CIGRE papers during 1992 to 1994. The 2nd GIS international survey questionnaire was circulated five years later, in 1996, with the aim of collecting service experience data available up to 31.12.1995. 80 users from 30 countries responded to the questionnaire. The collected data referred to 2115 GIS installations, 13 696 CB-bays and 118 483 CB-bay-years. In comparison to the 1st questionnaire, the 2nd questionnaire was more focused on installation overview and major failure statistics and GIS life cycle issues. Therefore only users were addressed. Besides the general data about GIS installations (similar to data sheet in the first survey) the users were asked to report the characteristics and service experience (major failures) for each individual GIS from the beginning of their putting into service and to answer more general questions concerning maintenance, lifetime and environmental aspects independently of the number of installed GIS and voltage level. The survey and data analysis were published in CIGRE papers during 1998 to 2000. The 3rd GIS international survey questionnaire was circulated in 2003 and collected population and failure data in 2004 to 2007. The structure of the questionnaire was as much as useful similar to the 2nd survey to enable a comparison.

Izvorni jezik
Engleski

Znanstvena područja
Elektrotehnika



POVEZANOST RADA


Ustanove:
KONČAR - Institut za elektrotehniku d.d.,
Tehničko veleučilište u Zagrebu

Profili:

Avatar Url Krešimir Meštrović (autor)


Citiraj ovu publikaciju:

Carvalho A.; Cormenzana M. L.; Furuta, H.; Grieshaber, W.; Hyrczak A.; Kopejtkova D.; Krone, J. G.; Kudoke, M.; Makareinis D.; Martins, J. F. et al.
CIGRÉ Technical Brochure No. 513: Final Report of the 2004 – 2007 International Enquiry on Reliability of High Voltage Equipment, Part 5 - Gas Insulated Switchgear (GIS). Pariz: CIGRÉ, 2012 (ostalo)
Carvalho A., Cormenzana M. L., Furuta, H., Grieshaber, W., Hyrczak A., Kopejtkova D., Krone, J., Kudoke, M., Makareinis D. & Martins, J. (2012) CIGRÉ Technical Brochure No. 513: Final Report of the 2004 – 2007 International Enquiry on Reliability of High Voltage Equipment, Part 5 - Gas Insulated Switchgear (GIS). Pariz, CIGRÉ.
@book{book, author = {Furuta, H. and Grieshaber, W. and Krone, J. G. and Kudoke, M. and Martins, J. F. and Me\v{s}trovi\'{c}, Kre\v{s}imir and \"{O}stlund, J. and Park, K.-Y. and Patel, J. and Protze, C. and Runde, M. and Schmid, J. and Skog, J. E. and S\"{o}lver, C. E. and Sweeney, B. and Waite, F.}, year = {2012}, pages = {172}, keywords = {high voltage equipment, reliability, maintenance, enquiry, gas insulated switchgear, major failures, minor failures, major failure frequencies, failure characteristics}, isbn = {978-2-85873-206-7}, title = {CIGR\'{E} Technical Brochure No. 513: Final Report of the 2004 – 2007 International Enquiry on Reliability of High Voltage Equipment, Part 5 - Gas Insulated Switchgear (GIS)}, keyword = {high voltage equipment, reliability, maintenance, enquiry, gas insulated switchgear, major failures, minor failures, major failure frequencies, failure characteristics}, publisher = {CIGR\'{E}}, publisherplace = {Pariz} }
@book{book, author = {Furuta, H. and Grieshaber, W. and Krone, J. G. and Kudoke, M. and Martins, J. F. and Me\v{s}trovi\'{c}, Kre\v{s}imir and \"{O}stlund, J. and Park, K.-Y. and Patel, J. and Protze, C. and Runde, M. and Schmid, J. and Skog, J. E. and S\"{o}lver, C. E. and Sweeney, B. and Waite, F.}, year = {2012}, pages = {172}, keywords = {high voltage equipment, reliability, maintenance, enquiry, gas insulated switchgear, major failures, minor failures, major failure frequencies, failure characteristics}, isbn = {978-2-85873-206-7}, title = {CIGR\'{E} Technical Brochure No. 513: Final Report of the 2004 – 2007 International Enquiry on Reliability of High Voltage Equipment, Part 5 - Gas Insulated Switchgear (GIS)}, keyword = {high voltage equipment, reliability, maintenance, enquiry, gas insulated switchgear, major failures, minor failures, major failure frequencies, failure characteristics}, publisher = {CIGR\'{E}}, publisherplace = {Pariz} }




Contrast
Increase Font
Decrease Font
Dyslexic Font