The Influence of Atmospheric Overvoltages on High- Voltage SF6 Substations


Vedran Vukasović; Zoran Baus; Marinko Barukčić
The Influence of Atmospheric Overvoltages on High- Voltage SF6 Substations // International journal of electrical and computer engineering systems, 2 (2011), 1; 17-24 (međunarodna recenzija, prethodno priopćenje, znanstveni)


CROSBI ID: 584097 Za ispravke kontaktirajte CROSBI podršku putem web obrasca

Naslov
The Influence of Atmospheric Overvoltages on High- Voltage SF6 Substations

Autori
Vedran Vukasović ; Zoran Baus ; Marinko Barukčić

Izvornik
International journal of electrical and computer engineering systems (1847-6996) 2 (2011), 1; 17-24

Vrsta, podvrsta i kategorija rada
Radovi u časopisima, prethodno priopćenje, znanstveni

Ključne riječi
atmospheric overvoltage ; induced voltage on the SF6 substation enclosure ; travelling wave

Sažetak
Very fast overvoltages are characteristic of high- voltage metal-enclosed SF6 insulated substations. During the transient phenomenon, on the SF6 substation enclosure an undesired, short- lasting induced overvoltage may appear, which cannot be prevented easily. This induced overvoltage is connected to the amplitude, form and duration of an atmospheric overvoltage that enters the substation as a travelling wave, dielectric strength of the SF6 gas and the geometry of the substation and its earthing. The objective of our research is to analyze the appearance of this undesired induced overvoltage on the substation enclosure. The above-mentioned phenomena can be examined by analyzing the results obtained through simulation. Due to the complexity of the equivalent electric model of a high-voltage SF6 substation and the analytic interpretation of the transient phenomenon in such complex substation, it is difficult to precisely analyze the overvoltage on the substation enclosure. The simulation results encourage us to do further research. Computer simulations also allow examination of various influences that affect the observed phenomenon. However, a suitable simulation model is necessary for performing simulations. Literature sources often do not provide a simulation model with simulation program objects. Thus, this paper focuses on the manner of presenting a simulation model with objects in the ATP program.

Izvorni jezik
Engleski

Znanstvena područja
Elektrotehnika

Napomena
This work was presented on the scientific- professional symposium “Development of Power Engineering in Croatia“ which was held on 21 October 2011 at the Faculty of Electrical Engineering in Osijek on the occasion of the 150th Anniversary of the Croatian Academy of Sciences and Arts.



POVEZANOST RADA


Ustanove:
Fakultet elektrotehnike, računarstva i informacijskih tehnologija Osijek

Profili:

Avatar Url Zoran Baus (autor)

Avatar Url Marinko Barukčić (autor)

Poveznice na cjeloviti tekst rada:

Hrčak

Citiraj ovu publikaciju:

Vedran Vukasović; Zoran Baus; Marinko Barukčić
The Influence of Atmospheric Overvoltages on High- Voltage SF6 Substations // International journal of electrical and computer engineering systems, 2 (2011), 1; 17-24 (međunarodna recenzija, prethodno priopćenje, znanstveni)
Vedran Vukasović, Zoran Baus & Marinko Barukčić (2011) The Influence of Atmospheric Overvoltages on High- Voltage SF6 Substations. International journal of electrical and computer engineering systems, 2 (1), 17-24.
@article{article, year = {2011}, pages = {17-24}, keywords = {atmospheric overvoltage, induced voltage on the SF6 substation enclosure, travelling wave}, journal = {International journal of electrical and computer engineering systems}, volume = {2}, number = {1}, issn = {1847-6996}, title = {The Influence of Atmospheric Overvoltages on High- Voltage SF6 Substations}, keyword = {atmospheric overvoltage, induced voltage on the SF6 substation enclosure, travelling wave} }
@article{article, year = {2011}, pages = {17-24}, keywords = {atmospheric overvoltage, induced voltage on the SF6 substation enclosure, travelling wave}, journal = {International journal of electrical and computer engineering systems}, volume = {2}, number = {1}, issn = {1847-6996}, title = {The Influence of Atmospheric Overvoltages on High- Voltage SF6 Substations}, keyword = {atmospheric overvoltage, induced voltage on the SF6 substation enclosure, travelling wave} }

Časopis indeksira:


  • Web of Science Core Collection (WoSCC)
    • Emerging Sources Citation Index (ESCI)


Uključenost u ostale bibliografske baze podataka::


  • CiteFactor, Genamics JournalSeek, Google Scholar





Contrast
Increase Font
Decrease Font
Dyslexic Font