Pretražite po imenu i prezimenu autora, mentora, urednika, prevoditelja

Napredna pretraga

Pregled bibliografske jedinice broj: 563642

Analysis of Transient Recovery Voltage in 400 kV SF6 Circuit Breaker Due to Transmission Line Faults


Filipović-Grčić, Božidar; Filipović-Grčić, Dalibor; Uglešić, Ivo
Analysis of Transient Recovery Voltage in 400 kV SF6 Circuit Breaker Due to Transmission Line Faults // International review of civil engineering, Vol. 6 (2011), N. 5 - Part B; 2652-2658 (međunarodna recenzija, članak, znanstveni)


CROSBI ID: 563642 Za ispravke kontaktirajte CROSBI podršku putem web obrasca

Naslov
Analysis of Transient Recovery Voltage in 400 kV SF6 Circuit Breaker Due to Transmission Line Faults

Autori
Filipović-Grčić, Božidar ; Filipović-Grčić, Dalibor ; Uglešić, Ivo

Izvornik
International review of civil engineering (2036-9913) Vol. 6 (2011), N. 5 - Part B; 2652-2658

Vrsta, podvrsta i kategorija rada
Radovi u časopisima, članak, znanstveni

Ključne riječi
Transient recovery voltage; short-line fault; SF6 circuit breaker; electric arc model; EMTP simulations

Sažetak
Transient recovery voltage (TRV) is calculated according to the IEC standards and using the EMTP- ATP software. Modeling of electric arc for the SF6 circuit breaker is presented. Influence of grading capacitors and line bay disposition on the TRV waveform on the side of the line in a 400 kV substation is analyzed for the short-line fault (SLF) conditions. Fault location at which the rate of rise of recovery voltage (RRRV) is the highest was determined using the EMTP-ATP simulations. Results obtained according to the IEC standards and using the EMTP-ATP are compared.

Izvorni jezik
Engleski

Znanstvena područja
Elektrotehnika

Napomena
Rad spada u kategoriju A jer je objavljen u znanstvenom časopisu koji je zastupljen u SCI– Expanded bazi (NN 84/05.) Journal Impact Factor from JCR Database: 1.364 ; Category Name: ENGINEERING, ELECTRICAL & ELECTRONIC ; Journal Rank in Category: 90 ; Quartile in Category: Q2



POVEZANOST RADA


Projekti:
036-0361590-1578 - Udovoljavanje zahtjeva zaštite okoliša u visokonaponskom sustavu (Uglešić, Ivo, MZO ) ( CroRIS)

Ustanove:
KONČAR - Institut za elektrotehniku d.d.,
Fakultet elektrotehnike i računarstva, Zagreb

Citiraj ovu publikaciju:

Filipović-Grčić, Božidar; Filipović-Grčić, Dalibor; Uglešić, Ivo
Analysis of Transient Recovery Voltage in 400 kV SF6 Circuit Breaker Due to Transmission Line Faults // International review of civil engineering, Vol. 6 (2011), N. 5 - Part B; 2652-2658 (međunarodna recenzija, članak, znanstveni)
Filipović-Grčić, B., Filipović-Grčić, D. & Uglešić, I. (2011) Analysis of Transient Recovery Voltage in 400 kV SF6 Circuit Breaker Due to Transmission Line Faults. International review of civil engineering, Vol. 6 (N. 5 - Part B), 2652-2658.
@article{article, author = {Filipovi\'{c}-Gr\v{c}i\'{c}, Bo\v{z}idar and Filipovi\'{c}-Gr\v{c}i\'{c}, Dalibor and Ugle\v{s}i\'{c}, Ivo}, year = {2011}, pages = {2652-2658}, keywords = {Transient recovery voltage, short-line fault, SF6 circuit breaker, electric arc model, EMTP simulations}, journal = {International review of civil engineering}, volume = {Vol. 6}, number = {N. 5 - Part B}, issn = {2036-9913}, title = {Analysis of Transient Recovery Voltage in 400 kV SF6 Circuit Breaker Due to Transmission Line Faults}, keyword = {Transient recovery voltage, short-line fault, SF6 circuit breaker, electric arc model, EMTP simulations} }
@article{article, author = {Filipovi\'{c}-Gr\v{c}i\'{c}, Bo\v{z}idar and Filipovi\'{c}-Gr\v{c}i\'{c}, Dalibor and Ugle\v{s}i\'{c}, Ivo}, year = {2011}, pages = {2652-2658}, keywords = {Transient recovery voltage, short-line fault, SF6 circuit breaker, electric arc model, EMTP simulations}, journal = {International review of civil engineering}, volume = {Vol. 6}, number = {N. 5 - Part B}, issn = {2036-9913}, title = {Analysis of Transient Recovery Voltage in 400 kV SF6 Circuit Breaker Due to Transmission Line Faults}, keyword = {Transient recovery voltage, short-line fault, SF6 circuit breaker, electric arc model, EMTP simulations} }

Časopis indeksira:


  • Web of Science Core Collection (WoSCC)
    • SCI-EXP, SSCI i/ili A&HCI


Uključenost u ostale bibliografske baze podataka::


  • Science Citation Index Expanded™ ( SciSearch) - ISI Thomson
  • Journal Citation Reports/Science Edition - ISI Thomson: IF=1.364
  • Elsevier Bibliographic Database SCOPUS
  • Academic Search Complete - EBSCO Information Services
  • Cambridge Scientific Abstracts - CSA/CIG
  • Copernicus (Journal Master List): IF=13.31





Contrast
Increase Font
Decrease Font
Dyslexic Font