Pregled bibliografske jedinice broj: 532524
Influence of Undisturbed Ground Temperature and Geothermal Gradient on the Sizing of Borehole Heat Exchangers
Influence of Undisturbed Ground Temperature and Geothermal Gradient on the Sizing of Borehole Heat Exchangers // WREC 2011, Linkoping / Professor Bahram Moshfegh (ur.).
Linköping: Linköping University Electronic Press, Linköpings universitet, 2011. str. 1360-1367 (predavanje, međunarodna recenzija, cjeloviti rad (in extenso), znanstveni)
CROSBI ID: 532524 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
Influence of Undisturbed Ground Temperature and Geothermal Gradient on the Sizing of Borehole Heat Exchangers
Autori
Kurevija, Tomislav ; Krapec, Vedrana ; Vulin, Domagoj
Vrsta, podvrsta i kategorija rada
Radovi u zbornicima skupova, cjeloviti rad (in extenso), znanstveni
Izvornik
WREC 2011, Linkoping
/ Professor Bahram Moshfegh - Linköping : Linköping University Electronic Press, Linköpings universitet, 2011, 1360-1367
ISBN
978-91-7393-070-3
Skup
World Renewable Energy Congress
Mjesto i datum
Linköping, Švedska, 08.05.2011. - 13.05.2011
Vrsta sudjelovanja
Predavanje
Vrsta recenzije
Međunarodna recenzija
Ključne riječi
Borehole heat exchanger; shallow geothermal energy; geothermal heat pump; undisturbed ground temperature; geothermal gradient
Sažetak
Undisturbed ground temperature is one of the most crucial thermogeological parameters needed for shallow geothermal resources assessment. Energy considered to be geothermal is energy stored in the ground at depths where solar radiation has no effect. At depth where undisturbed ground temperature occurs there is no influence of seasonal variations in air temperature from surface. Exact temperature value, and depth where it occurs, is functionally dependent on surface climate parameters and thermogeologic properties of ground. After abovementioned depth, increase of ground temperature is solely dependent on geothermal gradient. Accurately determined values of undisturbed ground temperature, and depth of occurrence, are beneficial for proper sizing of borehole heat exchangers and ground source heat pump system as a whole. On practical example of building being heated and cooled with shallow geothermal resource, via heat pump system, influence of undisturbed ground temperature and geothermal gradient on size of borehole heat exchanger is going to be presented. Sizing of borehole heat exchanger was calculated with commercial software Ground Loop Designer (GLD), which uses modified line source and cylinder source solutions of heat conduction in solids.
Izvorni jezik
Engleski
Znanstvena područja
Geologija, Rudarstvo, nafta i geološko inženjerstvo, Strojarstvo
POVEZANOST RADA
Projekti:
195-1951322-1340 - Zbrinjavanje ugljikovog dioksida iz geotermalnih i ugljikovodičnih ležišta (Golub, Miroslav, MZOS ) ( CroRIS)
195-1951390-1398 - Racionalno korištenje energetskih mineralnih sirovina u Hrvatskoj (Rajković, Damir, MZOS ) ( CroRIS)
Ustanove:
Rudarsko-geološko-naftni fakultet, Zagreb