Pregled bibliografske jedinice broj: 519597
Method for the reduction of in-service instrument transformer explosions
Method for the reduction of in-service instrument transformer explosions // European transactions on electrical power, 20 (2010), 7; 927-937 doi:10.1002/etep.375 (međunarodna recenzija, članak, znanstveni)
CROSBI ID: 519597 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
Method for the reduction of in-service instrument transformer explosions
Autori
Poljak, Miroslav ; Bojanić, Boris
Izvornik
European transactions on electrical power (1430-144X) 20
(2010), 7;
927-937
Vrsta, podvrsta i kategorija rada
Radovi u časopisima, članak, znanstveni
Ključne riječi
instrument transformer; failure; explosion; test; iInternal arc; Weibull distribution
Sažetak
The methodology and test procedure for the reduction of possible in-service explosions of instrument transformers to negligibly low values is described. As the introduction, an interpretation of statistical results of a survey about different types of failure in instrument transformers is Oven, showing that about 90% of them develop gradually, taking from several hours to several months. The International Electrotechnical Commission (IEC) is about to adopt a standardised procedure requiring that instrument transformers should withstand the effect of an internal arc. The authors are taking a critical view of the proposal ; explaining its main flaws. On the basis of calculations and experimental research on models and 123 kV current transformer it is shown that the mechanism causing explosions of instrument transformers cannot be simulated well enough in the way provided for in the draft of the new IEC standard. A new concept for the reduction of explosions of instrument transformers in service called, 'explosion safe' is proposed. It includes additional routine and special tests, and usage of devices for the detection or measurement of oil pressure se in transformers. The proposed tests are based on the investigation 'Volt-Time Relationships for PD Inception in Oil-Paper Insulation'.
Izvorni jezik
Engleski
Znanstvena područja
Elektrotehnika
POVEZANOST RADA
Projekti:
036-0362321-2326 - Numerički proračun elektromagnetskih polja transformatora (Štih, Željko, MZO ) ( CroRIS)
165-0362321-1552 - Motrenje, ispitivanje i dijagnostika transformatora (Miličević, Kruno, MZO ) ( CroRIS)
Ustanove:
KONČAR - Institut za elektrotehniku d.d.,
Fakultet elektrotehnike i računarstva, Zagreb,
Fakultet elektrotehnike, računarstva i informacijskih tehnologija Osijek
Citiraj ovu publikaciju:
Časopis indeksira:
- Current Contents Connect (CCC)
- Web of Science Core Collection (WoSCC)
- Science Citation Index Expanded (SCI-EXP)
- SCI-EXP, SSCI i/ili A&HCI
- Scopus
Uključenost u ostale bibliografske baze podataka::
- Compendex (EI Village)
- INSPEC
- PASCAL, Scopus