Power Loss Computation in High-current Generator Bus Ducts of Rectangular Cross-section
Power Loss Computation in High-current Generator Bus Ducts of Rectangular Cross-section // Electric power components and systems, 38 (2010), 13; 1469-1485 doi:10.1080/15325001003735192 (međunarodna recenzija, članak, znanstveni)
CROSBI ID: 490058 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
Power Loss Computation in High-current Generator Bus Ducts of Rectangular Cross-section
Autori
Sarajčev, Petar ; Goić, Ranko
Izvornik
Electric power components and systems (1532-5008) 38
(2010), 13;
1469-1485
Vrsta, podvrsta i kategorija rada
Radovi u časopisima, članak, znanstveni
Ključne riječi
high-current bus duct; filament method; mean geometric distance; power loss
Sažetak
Due to the medium voltage level of generator terminals and very high-current output, generator connection to the step-up transformer is often carried out with a so-called high-current air-insulated bus duct system. Due to these high currents, during normal generator operation, accompanying Joule power losses are often very high, which in turn, results in excessive (and even non-permissive) heating of the bus duct system. The solution to the mentioned power loss problem involves a determination of currents in phase conductors and in the shield of the metal-enclosed bus duct system. A bus duct transmission line consists of either a segregated or a non-segregated air- insulated three-phase system. Phase conductors and metal enclosures are both rectangular in cross-section. Here, the developed computation model is based on the conductor filament method with application of the geometric mean distance method. It takes into account both skin effect and proximity effects, as well as complete electromagnetic coupling between phase conductors and metal enclosure.
Izvorni jezik
Engleski
Znanstvena područja
Elektrotehnika
POVEZANOST RADA
Projekti:
023-0000000-3271 - Razvoj naprednih algoritama za modeliranje elektromagnetskih pojava (Vujević, Slavko, MZOS ) ( CroRIS)
Ustanove:
Fakultet elektrotehnike, strojarstva i brodogradnje, Split
Citiraj ovu publikaciju:
Časopis indeksira:
- Current Contents Connect (CCC)
- Web of Science Core Collection (WoSCC)
- Science Citation Index Expanded (SCI-EXP)
- SCI-EXP, SSCI i/ili A&HCI
- Scopus