Ground-source heat pump with a 100 m deep borehole heat exchanger – start up and first results


Soldo, Vladimir; Rusevljan, Miroslav; Curko, Tonko; Grozdek, Marino
Ground-source heat pump with a 100 m deep borehole heat exchanger – start up and first results // IIR/Eurotherm Sustainable Refrigeration and Heat Pump Technology Conference / Bjorn Palm (ur.).
Stockholm: KTH, 2010. str. VCH-2 (predavanje, međunarodna recenzija, cjeloviti rad (in extenso), znanstveni)


CROSBI ID: 474370 Za ispravke kontaktirajte CROSBI podršku putem web obrasca

Naslov
Ground-source heat pump with a 100 m deep borehole heat exchanger – start up and first results

Autori
Soldo, Vladimir ; Rusevljan, Miroslav ; Curko, Tonko ; Grozdek, Marino

Vrsta, podvrsta i kategorija rada
Radovi u zbornicima skupova, cjeloviti rad (in extenso), znanstveni

Izvornik
IIR/Eurotherm Sustainable Refrigeration and Heat Pump Technology Conference / Bjorn Palm - Stockholm : KTH, 2010, VCH-2

ISBN
978-91-7415-693-5

Skup
Sustainable Refrigeration and Heat Pump Technology

Mjesto i datum
Stockholm, Švedska, 13.06.2010. - 16.06.2010

Vrsta sudjelovanja
Predavanje

Vrsta recenzije
Međunarodna recenzija

Ključne riječi
heat pump; intallation of the borehole heat exchanger; soil temperature

Sažetak
Within the research project "Exploiting the ground as a renewable heat source", a test ground-source heat pump system was installed near the laboratory building of the Faculty of Mechanical Engineering and Naval Architecture (FAMENA), University of Zagreb. A 100 m deep borehole heat exchanger was made. A commercial polyethylene PE 100 double U-pipe was installed in the borehole with 152 mm in the outer diameter, and grouted with the thermally enhanced cement. Thermocouple temperature sensors were embedded in the borehole wall using original technology. The sensors were located at ten depth levels, ranging from 1, 5 m to 100 m. After the thermal stabilisation, the temperature at the depth of 50 m was 13, 5 °C, and at the depth of 100 m it was 15, 2 °C. Running of the system has started with the heating mode. The system will be in operation till the end of the heating season, and after that it will be tested in the cooling mode.

Izvorni jezik
Engleski

Znanstvena područja
Strojarstvo



POVEZANOST RADA


Projekti:
120-0000000-1802 - Dizalice topline s korištenjem tla kao obnovljivog toplinskog spremnika (Ćurko, Tonko, MZOS ) ( CroRIS)

Ustanove:
Fakultet strojarstva i brodogradnje, Zagreb

Profili:

Avatar Url Vladimir Soldo (autor)

Avatar Url Tonko Ćurko (autor)

Avatar Url Marino Grozdek (autor)

Avatar Url Miroslav Ruševljan (autor)


Citiraj ovu publikaciju:

Soldo, Vladimir; Rusevljan, Miroslav; Curko, Tonko; Grozdek, Marino
Ground-source heat pump with a 100 m deep borehole heat exchanger – start up and first results // IIR/Eurotherm Sustainable Refrigeration and Heat Pump Technology Conference / Bjorn Palm (ur.).
Stockholm: KTH, 2010. str. VCH-2 (predavanje, međunarodna recenzija, cjeloviti rad (in extenso), znanstveni)
Soldo, V., Rusevljan, M., Curko, T. & Grozdek, M. (2010) Ground-source heat pump with a 100 m deep borehole heat exchanger – start up and first results. U: Bjorn Palm (ur.)IIR/Eurotherm Sustainable Refrigeration and Heat Pump Technology Conference.
@article{article, author = {Soldo, Vladimir and Rusevljan, Miroslav and Curko, Tonko and Grozdek, Marino}, year = {2010}, pages = {VCH-2}, keywords = {heat pump, intallation of the borehole heat exchanger, soil temperature}, isbn = {978-91-7415-693-5}, title = {Ground-source heat pump with a 100 m deep borehole heat exchanger – start up and first results}, keyword = {heat pump, intallation of the borehole heat exchanger, soil temperature}, publisher = {KTH}, publisherplace = {Stockholm, \v{S}vedska} }
@article{article, author = {Soldo, Vladimir and Rusevljan, Miroslav and Curko, Tonko and Grozdek, Marino}, year = {2010}, pages = {VCH-2}, keywords = {heat pump, intallation of the borehole heat exchanger, soil temperature}, isbn = {978-91-7415-693-5}, title = {Ground-source heat pump with a 100 m deep borehole heat exchanger – start up and first results}, keyword = {heat pump, intallation of the borehole heat exchanger, soil temperature}, publisher = {KTH}, publisherplace = {Stockholm, \v{S}vedska} }




Contrast
Increase Font
Decrease Font
Dyslexic Font