Pregled bibliografske jedinice broj: 471625
Establishment of a new lightning location system in Croatia
Establishment of a new lightning location system in Croatia // Study Committee C4 on System Technical Performance, "A Colloquium on: Lightning and Power Systems - Technical Papers"
Kuala Lumpur: CIGRÉ, 2010. str. 1-11 (predavanje, međunarodna recenzija, cjeloviti rad (in extenso), znanstveni)
CROSBI ID: 471625 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
Establishment of a new lightning location system in Croatia
Autori
Uglešić, Ivo ; Milardić, Viktor ; Franc, Bojan ; Filipović-Grčić, Božidar ; Horvat, Jasna
Vrsta, podvrsta i kategorija rada
Radovi u zbornicima skupova, cjeloviti rad (in extenso), znanstveni
Izvornik
Study Committee C4 on System Technical Performance, "A Colloquium on: Lightning and Power Systems - Technical Papers"
/ - Kuala Lumpur : CIGRÉ, 2010, 1-11
Skup
CIGRE C4 International Colloquium on Lightning and Power Systems
Mjesto i datum
Kuala Lumpur, Malezija, 16.05.2010. - 19.05.2010
Vrsta sudjelovanja
Predavanje
Vrsta recenzije
Međunarodna recenzija
Ključne riječi
Lightning location system ; LINET ; GIS ; spatial correlation ; SCADA ; relay protection ; lightning data analysis
Sažetak
At the end of 2008, a new lightning location system (LLS) was established as part of LINET lightning detection network, which was developed in Germany and nowadays counts over 100 sensors installed across Europe. Four sensors were installed in different parts of Croatia. Together with sensors in neighbour countries, a sensor baseline of ≈250 km has been achieved covering Croatian territory. First data analysis show satisfactory detection efficiency (DE) and location accuracy (LA) with a statistical error less than 300 m. However, conducted analyses showed that network performance improvement is possible by installing two additional sensors. Software for real time lightning tracking with alarm function, analysis of lightning history, statistical calculations, correlation with power lines and creation of lightning density maps is being developed. Additional functionalities are in plan by connecting lightning data with SCADA, which enables a complete time and space correlation between lightning strikes and faults on transmission lines. Application of this software could provide as an effective decision making tool in control, maintenance and development of power systems. Paper shows examples of software application in power systems. Lightning data analysis for a period of one year are conducted in order to achieve a more comprehensive statistics. Analysis will show: number and ratio of lightning detected in Croatia distributed by type and polarity in different time periods ; lightning current amplitude distribution ; mean and average values of current amplitude and locating error.
Izvorni jezik
Engleski
Znanstvena područja
Elektrotehnika
POVEZANOST RADA
Projekti:
036-0361590-1578 - Udovoljavanje zahtjeva zaštite okoliša u visokonaponskom sustavu (Uglešić, Ivo, MZO ) ( CroRIS)
Ustanove:
Fakultet elektrotehnike i računarstva, Zagreb
Profili:
Bojan Franc
(autor)
Ivo Uglešić
(autor)
Jasna Horvat
(autor)
Božidar Filipović-Grčić
(autor)
Viktor Milardić
(autor)