STRUJE JEDNOPOLNOG I TROPOLNOG KRATKOG SPOJA NA SEKUNDARU TRANSFORMATORA U SPOJU Dzn, Yzn I YNzn


Kelemen, Tomislav; Sitar, Ivan; Nedić, Sandra
STRUJE JEDNOPOLNOG I TROPOLNOG KRATKOG SPOJA NA SEKUNDARU TRANSFORMATORA U SPOJU Dzn, Yzn I YNzn // Hrvatski ogranak međunarodne elektrodistribucijske konferencije HO CIRED 1. savjetovanje, Šibenik, 18-21 svibnja 2008.
Zagreb, 2008. (predavanje, domaća recenzija, cjeloviti rad (in extenso), znanstveni)


CROSBI ID: 367057 Za ispravke kontaktirajte CROSBI podršku putem web obrasca

Naslov
STRUJE JEDNOPOLNOG I TROPOLNOG KRATKOG SPOJA NA SEKUNDARU TRANSFORMATORA U SPOJU Dzn, Yzn I YNzn
(SINGLE AND THREE-PHASE SECONDARY SHORT-CIRCUIT CURRENTS ON TRANSFORMERS CONNECTED Dzn, Yzn AND YNzn)

Autori
Kelemen, Tomislav ; Sitar, Ivan ; Nedić, Sandra

Vrsta, podvrsta i kategorija rada
Radovi u zbornicima skupova, cjeloviti rad (in extenso), znanstveni

Izvornik
Hrvatski ogranak međunarodne elektrodistribucijske konferencije HO CIRED 1. savjetovanje, Šibenik, 18-21 svibnja 2008. / - Zagreb, 2008

Skup
Hrvatski ogranak međunarodne elektrodistribucijske konferencije HO CIRED 1. savjetovanje, Šibenik, 18-21 svibnja 2008.

Mjesto i datum
Šibenik, Hrvatska, 18.05.2008. - 20.05.2008

Vrsta sudjelovanja
Predavanje

Vrsta recenzije
Domaća recenzija

Ključne riječi
Transformatori sa sekundarom u z spoju; jednopolni kratki spoj; tropolni kratki spoj; specijalni transformatori
(Transformers with z connected secondary; single phase short-circuit; three- phase short circuit; special transformers)

Sažetak
Nisko naponski namoti transformatora u spoju zvijezda s izvedenom nultočkom nekako su se udomaćili u proizvodnji i u upotrebi transformatora, dok namoti u spoju slomljena zvijezda nisu tako česti ni opće poznati. Budući da svaki fazni namot u spoju slomljena zvijezda ili cik-cak (oznaka z) ulančuje namote s dva stupa, složeniji je i račun reaktancija transformatora i uklapanje reaktancija mreže u račun struja kvara. Točan račun struja kvara važan je za ispravno dimenzioniranje sekundarne zaštite transformatora. U radu se obrađuje račun struja jednopolnog i tropolnog kratkog spoja na sekundaru transformatora u spoju Dzn, Yzn i YNzn napajanih iz mreže poznatog unutrašnjeg otpora, kakav obično traže kupci takvih transformatora. Dokazuje se, da u sva tri navedena slučaja struje jednopolnog i struje tropolnog kratkog spoja i prateća naprezanja materijala ne ovise o spoju primarnog namota nego samo o geometriji namota i reaktanciji mreže. Transformers with star-connected LV winding and earthed neutral represent a majority of transformers produced or in use today. Zig-zag connected winding is less frequent and therefore less known. Since each phase winding in zigzag (z) connection couples two core limbs, it makes the calculation of transformer reactance and adding the power system network reactance into calculations of fault currents more difficult. Accurate calculation of fault currents is of great importance for the right dimensioning of transformer secondary winding protection. This paper analyzes the calculation of single-phase and three-phase short-circuit currents on the secondary winding of Dzn, Yzn and YNzn transformer winding connections, powered by power system network of known inner reactance, as usually required by the buyers of such transformers. It is proven in this paper that in all three stated cases single-phase and three-phase short-circuit currents and stresses of material do not depend on primary winding connection, but only on geometry of winding and power system network reactance.

Izvorni jezik
Hrvatski

Znanstvena područja
Elektrotehnika



POVEZANOST RADA


Projekti:
008-0362321-1592 - Istraživanje pojava u energetskim i mjernim transformatorima u eksploataciji (Kelemen, Tomislav, MZOS ) ( CroRIS)

Ustanove:
KONČAR - Institut za elektrotehniku d.d.

Profili:

Avatar Url Tomislav Kelemen (autor)

Avatar Url Ivan Sitar (autor)

Poveznice na cjeloviti tekst rada:

Pristup cjelovitom tekstu rada

Citiraj ovu publikaciju:

Kelemen, Tomislav; Sitar, Ivan; Nedić, Sandra
STRUJE JEDNOPOLNOG I TROPOLNOG KRATKOG SPOJA NA SEKUNDARU TRANSFORMATORA U SPOJU Dzn, Yzn I YNzn // Hrvatski ogranak međunarodne elektrodistribucijske konferencije HO CIRED 1. savjetovanje, Šibenik, 18-21 svibnja 2008.
Zagreb, 2008. (predavanje, domaća recenzija, cjeloviti rad (in extenso), znanstveni)
Kelemen, T., Sitar, I. & Nedić, S. (2008) STRUJE JEDNOPOLNOG I TROPOLNOG KRATKOG SPOJA NA SEKUNDARU TRANSFORMATORA U SPOJU Dzn, Yzn I YNzn. U: Hrvatski ogranak međunarodne elektrodistribucijske konferencije HO CIRED 1. savjetovanje, Šibenik, 18-21 svibnja 2008..
@article{article, author = {Kelemen, Tomislav and Sitar, Ivan and Nedi\'{c}, Sandra}, year = {2008}, keywords = {Transformatori sa sekundarom u z spoju, jednopolni kratki spoj, tropolni kratki spoj, specijalni transformatori}, title = {STRUJE JEDNOPOLNOG I TROPOLNOG KRATKOG SPOJA NA SEKUNDARU TRANSFORMATORA U SPOJU Dzn, Yzn I YNzn}, keyword = {Transformatori sa sekundarom u z spoju, jednopolni kratki spoj, tropolni kratki spoj, specijalni transformatori}, publisherplace = {\v{S}ibenik, Hrvatska} }
@article{article, author = {Kelemen, Tomislav and Sitar, Ivan and Nedi\'{c}, Sandra}, year = {2008}, keywords = {Transformers with z connected secondary, single phase short-circuit, three- phase short circuit, special transformers}, title = {SINGLE AND THREE-PHASE SECONDARY SHORT-CIRCUIT CURRENTS ON TRANSFORMERS CONNECTED Dzn, Yzn AND YNzn}, keyword = {Transformers with z connected secondary, single phase short-circuit, three- phase short circuit, special transformers}, publisherplace = {\v{S}ibenik, Hrvatska} }