Power Quality Problems Due to Transformer Inrush Current


Tokić, Amir; Uglešić, Ivo
Power Quality Problems Due to Transformer Inrush Current // Proceedings of International CIGRE Symposium Transient Phenomena in Large Electric Power Systems / NN (ur.).
Pariz: Internationl Concile on Large Electric Systems 02002, 2007. (predavanje, međunarodna recenzija, cjeloviti rad (in extenso), znanstveni)


CROSBI ID: 336361 Za ispravke kontaktirajte CROSBI podršku putem web obrasca

Naslov
Power Quality Problems Due to Transformer Inrush Current

Autori
Tokić, Amir ; Uglešić, Ivo

Vrsta, podvrsta i kategorija rada
Radovi u zbornicima skupova, cjeloviti rad (in extenso), znanstveni

Izvornik
Proceedings of International CIGRE Symposium Transient Phenomena in Large Electric Power Systems / NN - Pariz : Internationl Concile on Large Electric Systems 02002, 2007

ISBN
978-2-85873-022-3

Skup
International CIGRE Symposium Transient Phenomena in Large Electric Power Systems

Mjesto i datum
Zagreb, Hrvatska, 18.04.2007. - 21.04.2007

Vrsta sudjelovanja
Predavanje

Vrsta recenzije
Međunarodna recenzija

Ključne riječi
Power quality; transformer; inrush current; temporary overvoltage; surge arrester

Sažetak
Transformer energization can produce a large nonsinuoidal inrush current which contains both odd and higher order harmonic components that can put transformer winding under mechanical stress. Additionally, they can cause irregular tripping of harmonic protection relays. Furthermore, in relatively weak power systems, such as is the Bosnian system, the superposition of harmonic components with system resonance frequencies may produce temporary overvoltages (TOV). Transformer winding failures and metal oxide surge arrester (MOA) energy stresses can occur due to TOV. The paper demonstrates a case study of an energization of a 220/110 kV transformer and power quality problems that can appear due to higher harmonics. Energy stresses of MOA provoked by transformer energization are considered in the paper.

Izvorni jezik
Engleski

Znanstvena područja
Elektrotehnika



POVEZANOST RADA


Projekti:
036-0361590-1578 - Udovoljavanje zahtjeva zaštite okoliša u visokonaponskom sustavu (Uglešić, Ivo, MZO ) ( CroRIS)

Ustanove:
Fakultet elektrotehnike i računarstva, Zagreb

Profili:

Avatar Url Ivo Uglešić (autor)


Citiraj ovu publikaciju:

Tokić, Amir; Uglešić, Ivo
Power Quality Problems Due to Transformer Inrush Current // Proceedings of International CIGRE Symposium Transient Phenomena in Large Electric Power Systems / NN (ur.).
Pariz: Internationl Concile on Large Electric Systems 02002, 2007. (predavanje, međunarodna recenzija, cjeloviti rad (in extenso), znanstveni)
Tokić, A. & Uglešić, I. (2007) Power Quality Problems Due to Transformer Inrush Current. U: NN (ur.)Proceedings of International CIGRE Symposium Transient Phenomena in Large Electric Power Systems.
@article{article, author = {Toki\'{c}, Amir and Ugle\v{s}i\'{c}, Ivo}, year = {2007}, keywords = {Power quality, transformer, inrush current, temporary overvoltage, surge arrester}, isbn = {978-2-85873-022-3}, title = {Power Quality Problems Due to Transformer Inrush Current}, keyword = {Power quality, transformer, inrush current, temporary overvoltage, surge arrester}, publisher = {Internationl Concile on Large Electric Systems 02002}, publisherplace = {Zagreb, Hrvatska} }
@article{article, author = {Toki\'{c}, Amir and Ugle\v{s}i\'{c}, Ivo}, year = {2007}, keywords = {Power quality, transformer, inrush current, temporary overvoltage, surge arrester}, isbn = {978-2-85873-022-3}, title = {Power Quality Problems Due to Transformer Inrush Current}, keyword = {Power quality, transformer, inrush current, temporary overvoltage, surge arrester}, publisher = {Internationl Concile on Large Electric Systems 02002}, publisherplace = {Zagreb, Hrvatska} }




Contrast
Increase Font
Decrease Font
Dyslexic Font