Pregled bibliografske jedinice broj: 306922
Some Issues of Microprocessor-based Power System Stabilizer Implementation
Some Issues of Microprocessor-based Power System Stabilizer Implementation // Proceedings of the 15th Mediterranean Conference on Control and Automation - MED'07, July 27 - 29, 2007, Athens - Greece / Antsaklis, Panos ; Valavanis, Kimon (ur.).
Atena: Institute of Electrical and Electronics Engineers (IEEE), 2007. (poster, međunarodna recenzija, cjeloviti rad (in extenso), znanstveni)
CROSBI ID: 306922 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
Some Issues of Microprocessor-based Power System Stabilizer Implementation
Autori
Tečec, Zlatka ; Ćesić, Vinko ; Petrović, Ivan
Vrsta, podvrsta i kategorija rada
Radovi u zbornicima skupova, cjeloviti rad (in extenso), znanstveni
Izvornik
Proceedings of the 15th Mediterranean Conference on Control and Automation - MED'07, July 27 - 29, 2007, Athens - Greece
/ Antsaklis, Panos ; Valavanis, Kimon - Atena : Institute of Electrical and Electronics Engineers (IEEE), 2007
Skup
IEEE 15th Mediterranean Conference on Control and Automation - MED'07, July 27 - 29, 2007, Athens - Greece
Mjesto i datum
Atena, Grčka, 27.06.2007. - 29.06.2007
Vrsta sudjelovanja
Poster
Vrsta recenzije
Međunarodna recenzija
Ključne riječi
power system stabilizers; voltage control; microprocessor based implementation
Sažetak
In this paper, we present our experience gained through implementation of the IEEE PSS2B type of power system stabilizers (PSSs). The paper describes a particular case of implementing this type of PSS in microprocessor- based digital voltage regulator with limited processing resources. The following issues have been elaborated: (i) choice of sampling time and its influence on the performance of the PSS and on the processor utilization, (ii) selection of the lead-lags time constants and their influences on the noise amplification and (iii) scaling associated with the integer arithmetic. The abovementioned problems have been analyzed by simulations and experimentally on a laboratory power plant, and appropriate solutions have been proposed. Finally, the PSS2B has been implemented on real power plants, and a simple method for field verification of tuned PSS2B parameters is explained.
Izvorni jezik
Engleski
Znanstvena područja
Elektrotehnika, Računarstvo, Temeljne tehničke znanosti
POVEZANOST RADA
Projekti:
036-0361621-3012 - Napredne strategije upravljanja i estimacije u složenim sustavima (Perić, Nedjeljko, MZO ) ( CroRIS)