Pregled bibliografske jedinice broj: 306411
Numerical Modelling Of Temperature And Air Flow Distribution In Enclosed Room
Numerical Modelling Of Temperature And Air Flow Distribution In Enclosed Room // Proceedings of the Heat-SET 2007 conference: Heat transfer in components and systems for sustainable energy technologies, Vol. II / Thonon, Bernard (ur.).
Grenoble: Editions-GRETh, 2007. str. 1055-1062 (poster, međunarodna recenzija, cjeloviti rad (in extenso), znanstveni)
CROSBI ID: 306411 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
Numerical Modelling Of Temperature And Air Flow Distribution In Enclosed Room
Autori
Bonefačić, Igor ; Franković, Bernard ; Viličić, Ivan ; Glažar, Vladimir
Vrsta, podvrsta i kategorija rada
Radovi u zbornicima skupova, cjeloviti rad (in extenso), znanstveni
Izvornik
Proceedings of the Heat-SET 2007 conference: Heat transfer in components and systems for sustainable energy technologies, Vol. II
/ Thonon, Bernard - Grenoble : Editions-GRETh, 2007, 1055-1062
ISBN
2-9502555-3-1
Skup
Heat-SET 2007 conference: Heat transfer in components and systems for sustainable energy technologies
Mjesto i datum
Chambéry, Francuska, 18.04.2007. - 20.04.2007
Vrsta sudjelovanja
Poster
Vrsta recenzije
Međunarodna recenzija
Ključne riječi
numerical modelling; heat transfer; air flow; enclosed room
Sažetak
In the paper three-dimensional case of heat transfer and air flow has been presented for enclosed space heating and cooling with unit mounted on the wall. Numerical modelling has been used to analyze effect of space height on temperature and air velocity distribution under standard conditions. Physical processes in two rooms with different heights are modelled using specialized computational fluid dynamics (CFD) software FLUENT. Calculations are carried out in an empty room without any human or mechanical activity and compared with previous experimental measurements. Numerical analysis has shown distinct relationship between room dimensions (height in this case) and state of comfort in the room. Although average values of temperature and air velocity in the room are satisfactory there are local distortions from the standard optimal comfort values. Considerable differences in temperature distribution are observed especially in heating conditions where temperature drop in lower layers of higher room occur due to buoyancy effects. To cancel buoyancy effects it is necessary to increase air inlet velocity from the unit which could lead to local air velocity distortions resulting with disturbed optimal comfort values.
Izvorni jezik
Engleski
Znanstvena područja
Strojarstvo, Temeljne tehničke znanosti
POVEZANOST RADA
Projekti:
069-0692972-3112 - Istraživanje i razvoj komponenata i sustava obnovljivih izvora energije (Franković, Bernard, MZOS ) ( CroRIS)
Ustanove:
Tehnički fakultet, Rijeka
Profili:
Ivan Viličić
(autor)
Bernard Franković
(autor)
Vladimir Glažar
(autor)
Igor Bonefačić
(autor)