Pregled bibliografske jedinice broj: 26221
Propagation of Overvoltages Provoked by Disconnector Switching Inside and Outside of a Gas Insulated Substatiom
Propagation of Overvoltages Provoked by Disconnector Switching Inside and Outside of a Gas Insulated Substatiom // Paper Collection of Cigre International Conference
Zagreb, 1998. (predavanje, međunarodna recenzija, cjeloviti rad (in extenso), znanstveni)
CROSBI ID: 26221 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
Propagation of Overvoltages Provoked by Disconnector Switching Inside and Outside of a Gas Insulated Substatiom
Autori
Uglešić, Ivo ; Lukić, Mažana ; Bojić, Srećko
Vrsta, podvrsta i kategorija rada
Radovi u zbornicima skupova, cjeloviti rad (in extenso), znanstveni
Izvornik
Paper Collection of Cigre International Conference
/ - Zagreb, 1998
Skup
Insulation Coordination for Electricity Development in Central European Countries
Mjesto i datum
Zagreb, Hrvatska, 09.09.1998. - 12.09.1998
Vrsta sudjelovanja
Predavanje
Vrsta recenzije
Međunarodna recenzija
Ključne riječi
Overvoltages; gas insulated substation; disconnector switching; very fast transients; substation enclosure; earthing
Sažetak
Switching operations in gas insulated substations are accompanied with multiple restrikes, especially during discinnector swiching. Overvoltages provoked by restrikes on a disconnector propagate inside and outside of the gas insulated substation. Simulation of overvoltages on different parts inside and outside of the substation have been conducted by using the computer program on the model of three phase enclosed 123 kV substation. Computer simulations give an insight of overvoltages amplitudes and frequencies in the substation. Beside computer simulations, external overvoltages were measured during disconnector switching.
Izvorni jezik
Engleski
Znanstvena područja
Elektrotehnika