Pregled bibliografske jedinice broj: 242564
Common winding of autotransformer and loading of tertiary
Common winding of autotransformer and loading of tertiary // Proceedings XIV-th Int. Symp. on Electrical Apparatus and Technologies, SIELA 2005, Vol.1
Sofija: Technical University of Sofia, 2005. str. 129-134 (predavanje, međunarodna recenzija, cjeloviti rad (in extenso), znanstveni)
CROSBI ID: 242564 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
Common winding of autotransformer and loading of tertiary
Autori
Kelemen, Tomislav ; Hot, Kemal
Vrsta, podvrsta i kategorija rada
Radovi u zbornicima skupova, cjeloviti rad (in extenso), znanstveni
Izvornik
Proceedings XIV-th Int. Symp. on Electrical Apparatus and Technologies, SIELA 2005, Vol.1
/ - Sofija : Technical University of Sofia, 2005, 129-134
Skup
14th Int. Symp. on Electrical Apparatus and Technologies
Mjesto i datum
Plovdiv, Bugarska, 01.06.2005. - 03.06.2005
Vrsta sudjelovanja
Predavanje
Vrsta recenzije
Međunarodna recenzija
Ključne riječi
autotransformer; tertiary; overload
Sažetak
Besides YNa-connected high-voltage and medium-voltage windings, autotransformers in high-voltage networks usually also have a tertiary winding. It is a delta-connected low-voltage winding intended for loading and sized mostly for one third of autotransformer rated power. The paper describes winding loads imposed on an autotransformer with tertiary by loads at autotransformer's medium-voltage and tertiary terminals, and also by loads at its high-voltage and tertiary terminals. It is shown that, if in the autotransformer design the tertiary load is ignored, the common winding can become overloaded. The solution is a control of the common winding current by an over-current relay. The relay current is obtained by current transformers at high-voltage and medium-voltage terminals connected at their secondaries through an intermediate current transformer, and it corresponds to the common winding current.
Izvorni jezik
Engleski
Znanstvena područja
Elektrotehnika