Pretražite po imenu i prezimenu autora, mentora, urednika, prevoditelja

Napredna pretraga

Pregled bibliografske jedinice broj: 242564

Common winding of autotransformer and loading of tertiary


Kelemen, Tomislav; Hot, Kemal
Common winding of autotransformer and loading of tertiary // Proceedings XIV-th Int. Symp. on Electrical Apparatus and Technologies, SIELA 2005, Vol.1
Sofija: Technical University of Sofia, 2005. str. 129-134 (predavanje, međunarodna recenzija, cjeloviti rad (in extenso), znanstveni)


CROSBI ID: 242564 Za ispravke kontaktirajte CROSBI podršku putem web obrasca

Naslov
Common winding of autotransformer and loading of tertiary

Autori
Kelemen, Tomislav ; Hot, Kemal

Vrsta, podvrsta i kategorija rada
Radovi u zbornicima skupova, cjeloviti rad (in extenso), znanstveni

Izvornik
Proceedings XIV-th Int. Symp. on Electrical Apparatus and Technologies, SIELA 2005, Vol.1 / - Sofija : Technical University of Sofia, 2005, 129-134

Skup
14th Int. Symp. on Electrical Apparatus and Technologies

Mjesto i datum
Plovdiv, Bugarska, 01.06.2005. - 03.06.2005

Vrsta sudjelovanja
Predavanje

Vrsta recenzije
Međunarodna recenzija

Ključne riječi
autotransformer; tertiary; overload

Sažetak
Besides YNa-connected high-voltage and medium-voltage windings, autotransformers in high-voltage networks usually also have a tertiary winding. It is a delta-connected low-voltage winding intended for loading and sized mostly for one third of autotransformer rated power. The paper describes winding loads imposed on an autotransformer with tertiary by loads at autotransformer's medium-voltage and tertiary terminals, and also by loads at its high-voltage and tertiary terminals. It is shown that, if in the autotransformer design the tertiary load is ignored, the common winding can become overloaded. The solution is a control of the common winding current by an over-current relay. The relay current is obtained by current transformers at high-voltage and medium-voltage terminals connected at their secondaries through an intermediate current transformer, and it corresponds to the common winding current.

Izvorni jezik
Engleski

Znanstvena područja
Elektrotehnika



POVEZANOST RADA


Projekti:
0008001
0246001

Ustanove:
KONČAR - Institut za elektrotehniku d.d.,
Tehničko veleučilište u Zagrebu


Citiraj ovu publikaciju:

Kelemen, Tomislav; Hot, Kemal
Common winding of autotransformer and loading of tertiary // Proceedings XIV-th Int. Symp. on Electrical Apparatus and Technologies, SIELA 2005, Vol.1
Sofija: Technical University of Sofia, 2005. str. 129-134 (predavanje, međunarodna recenzija, cjeloviti rad (in extenso), znanstveni)
Kelemen, T. & Hot, K. (2005) Common winding of autotransformer and loading of tertiary. U: Proceedings XIV-th Int. Symp. on Electrical Apparatus and Technologies, SIELA 2005, Vol.1.
@article{article, author = {Kelemen, Tomislav and Hot, Kemal}, year = {2005}, pages = {129-134}, keywords = {autotransformer, tertiary, overload}, title = {Common winding of autotransformer and loading of tertiary}, keyword = {autotransformer, tertiary, overload}, publisher = {Technical University of Sofia}, publisherplace = {Plovdiv, Bugarska} }
@article{article, author = {Kelemen, Tomislav and Hot, Kemal}, year = {2005}, pages = {129-134}, keywords = {autotransformer, tertiary, overload}, title = {Common winding of autotransformer and loading of tertiary}, keyword = {autotransformer, tertiary, overload}, publisher = {Technical University of Sofia}, publisherplace = {Plovdiv, Bugarska} }