Reliability Issues Concerning the Transition from 110-35-10 kV to 110-20 kV Distribution System
Reliability Issues Concerning the Transition from 110-35-10 kV to 110-20 kV Distribution System // Proceedings of the 3rd IEE International Conference on Reliability of Transmission and Distribution Networks
London : Delhi: IEE Power Systems, 2005. (poster, međunarodna recenzija, cjeloviti rad (in extenso), znanstveni)
CROSBI ID: 241816 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
Reliability Issues Concerning the Transition from 110-35-10 kV to 110-20 kV Distribution System
Autori
Baričević, Tomislav ; Žutobradić, Srđan
Vrsta, podvrsta i kategorija rada
Radovi u zbornicima skupova, cjeloviti rad (in extenso), znanstveni
Izvornik
Proceedings of the 3rd IEE International Conference on Reliability of Transmission and Distribution Networks
/ - London : Delhi : IEE Power Systems, 2005
Skup
3rd IEE International Conference on Reliability of Transmission and Distribution Networks
Mjesto i datum
London, Ujedinjeno Kraljevstvo, 15.02.2005. - 17.02.2005
Vrsta sudjelovanja
Poster
Vrsta recenzije
Međunarodna recenzija
Ključne riječi
power supply quality; transition from 110-35-10 kV to 110-20 kV system
Sažetak
The traditional 110-35-10 kV distribution system in Croatia is in the process of transition to a new one with a single medium voltage level of 20 kV. Two solutions of the network development, 110-35-10 kV and 110-20 kV, are evaluated. The special emphasis is dedicated to the resulting reliability and power supply quality of the system operation, using the number and duration of outages and undelivered energy costs for comparison. Examples of the cost effective solutions for the reliability and supply quality issues in the distribution network are given, with the main tools being network topology and in-line circuit breakers or remote controlled switching devices for installation along 20 kV feeders.