Current and Voltage WaveformsS upon the Conductor Rupture in one Phase of the 110 KV Radical Cunnection of the Generator at HPP Dubriovnik to the Ppwer System - Simulation and Measurement
Current and Voltage WaveformsS upon the Conductor Rupture in one Phase of the 110 KV Radical Cunnection of the Generator at HPP Dubriovnik to the Ppwer System - Simulation and Measurement // Proceedings of the 13th International Conference on Power System Protection (PSP 2002) / Curk, Jurij ; Gubina, Ferdinand (ur.).
Ljubljana: Fakulteta za elektrotehniko, Univerza v Ljubljani, 2002. (predavanje, međunarodna recenzija, cjeloviti rad (in extenso), stručni)
CROSBI ID: 185478 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
Current and Voltage WaveformsS upon the Conductor Rupture in one Phase of the 110 KV Radical Cunnection of the Generator at HPP Dubriovnik to the Ppwer System - Simulation and Measurement
Autori
Stojsavljević, Milan ; Nemec, Darko ; Mehmedović, Muharem ; Čerina, Zdeslav ; Kosor, Robert ; Gazzari, Sergio
Vrsta, podvrsta i kategorija rada
Radovi u zbornicima skupova, cjeloviti rad (in extenso), stručni
Izvornik
Proceedings of the 13th International Conference on Power System Protection (PSP 2002)
/ Curk, Jurij ; Gubina, Ferdinand - Ljubljana : Fakulteta za elektrotehniko, Univerza v Ljubljani, 2002
ISBN
961-6371-35-5
Skup
International Conference on Power System Protection Conference (13 ; 2002)
Mjesto i datum
Bled, Slovenija, 25.09.2002. - 27.09.2002
Vrsta sudjelovanja
Predavanje
Vrsta recenzije
Međunarodna recenzija
Ključne riječi
electric power system; generator; radial connection; protection system; simulation
Sažetak
This paper presents results of time-domain simulation of single-phase opening (the effect of the 110 kV phase conductor rupture) of the 110 kV transmission line Komolac - Trebinje (a part of radial connection of HPP Dubrovnik to the system) in realistic operating conditions. The simulation results comprise instantaneous and RMS values of phase currents, phase voltages and residual current in the 110 kV line bay Komolac at the HPP Dubrovnik switchyard and in the 110 kV transmission line bay Trebinje at the substation Komolac. Simulation results are compared with quantities recorded by the numerical line protection device REL511 installed at HPP Dubrovnik. Simulation includes electromechanical transients with excitation system and turbine governor being modelled. Rather good correspondence between simulation results and measurements in this particular case shows that such calculation results could be used as a basis for tuning and coordination of protection systems