Heat Transfer Comparison in Coaxial Tube in Tube Heat Exchanger Operating with Refrigerants R407C and R22
Heat Transfer Comparison in Coaxial Tube in Tube Heat Exchanger Operating with Refrigerants R407C and R22 // Sustainable Development of Energy, Water and Environment Systems / Neven Duić (ur.).
Zagreb: Energetika marketing, 2002. (predavanje, međunarodna recenzija, cjeloviti rad (in extenso), znanstveni)
CROSBI ID: 136910 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
Heat Transfer Comparison in Coaxial Tube in Tube Heat Exchanger Operating with Refrigerants R407C and R22
Autori
Soldo, Vladimir ; Ćurko, Tonko ; Grozdek, Marino
Vrsta, podvrsta i kategorija rada
Radovi u zbornicima skupova, cjeloviti rad (in extenso), znanstveni
Izvornik
Sustainable Development of Energy, Water and Environment Systems
/ Neven Duić - Zagreb : Energetika marketing, 2002
Skup
Sustainable Development of Energy, Water and Environment Systems
Mjesto i datum
Dubrovnik, Hrvatska, 02.06.2002. - 07.06.2002
Vrsta sudjelovanja
Predavanje
Vrsta recenzije
Međunarodna recenzija
Ključne riječi
zeotropic mixtures; Lorenz process; thermodynamic efficiency
Sažetak
Due to hazardous environmental impact of the CFC and HCFC refrigerants that are currently used in R&AC systems, in accordance with the Montreal Protocol, actual is exchange of those by new, ecologically acceptable, HFC refrigerants. Therefore system performance analysis was made where the single component R22 refrigerant was replaced by zeotropic mixture R407C. In the system operating at the same conditions, a comparison of heat transfer in coaxial exchanger for R22 and R407C is performed. Experimental data are presented in the form of average heat transfer coefficients as a function of heat flux and mass velocity. Results have showed that in the heat exchange process with R407C refrigerant heat transfer coefficient is lower (10-35%) than for R22. As R407C is a blend of three pure refrigerants (R32, R125 and R134a) with temperature glide of 5-7°C, the concentration shift occurs during two-phase flow in the condenser and evaporator.