Pregled bibliografske jedinice broj: 1268092
Measurements and Simulations of Very Fast Transients at the Connection of High Voltage Cable with Gas Insulated Metal Enclosed Switchgear
Measurements and Simulations of Very Fast Transients at the Connection of High Voltage Cable with Gas Insulated Metal Enclosed Switchgear // Fourth International Conference on Smart Grid Metrology (SMAGRIMET 2023) / Konjevod, Jure ; Šala, Alan ; Mostarac, Petar (ur.).
Zagreb: Fakultet elektrotehnike i računarstva Sveučilišta u Zagrebu, 2023. str. 86-90 (predavanje, međunarodna recenzija, cjeloviti rad (in extenso), znanstveni)
CROSBI ID: 1268092 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
Measurements and Simulations of Very Fast
Transients at the Connection of High Voltage Cable
with Gas Insulated Metal Enclosed Switchgear
(Measurements and Simulations of Very Fast
Transients at the Connection of High Voltage Cable
with Gas Insulated Metal Enclosed Switchgear)
Autori
Musulin, Katarina ; Filipović-Grčić, Božidar ; Milardić, Viktor ; Jurić, Mario ; Teči, Robert ; Jurišić, Bruno
Vrsta, podvrsta i kategorija rada
Radovi u zbornicima skupova, cjeloviti rad (in extenso), znanstveni
Izvornik
Fourth International Conference on Smart Grid Metrology (SMAGRIMET 2023)
/ Konjevod, Jure ; Šala, Alan ; Mostarac, Petar - Zagreb : Fakultet elektrotehnike i računarstva Sveučilišta u Zagrebu, 2023, 86-90
ISBN
978-953-184-284-6
Skup
Fourth International Conference on Smart Grid Metrology (SMAGRIMET 2023)
Mjesto i datum
Cavtat, Hrvatska, 24.04.2023. - 28.04.2023
Vrsta sudjelovanja
Predavanje
Vrsta recenzije
Međunarodna recenzija
Ključne riječi
TEVR, GIS, VFTO measurements, earthing leads, EMTP simulation
Sažetak
The transient enclosure voltage rise (TEVR) in GIS is caused by very fast overvoltages that occur inside the enclosure during the switching operation, mainly during disconnector operations. TEVR is caused by very high frequency overvoltages (the order of MHz), for which even small inductance of earthing leads can represent significant impedance. The level of TEVR strongly depends on design and length of the earthing leads. Therefore, overvoltage measurements were performed for different earthing leads configurations in 110 kV GIS and results are presented in this paper. The earthing leads configurations were first verified by simulation in the EMTP program.
Izvorni jezik
Engleski
POVEZANOST RADA
Ustanove:
KONČAR - Institut za elektrotehniku d.d.,
Fakultet elektrotehnike i računarstva, Zagreb
Profili:
Božidar Filipović-Grčić
(autor)
Bruno Jurišić
(autor)
Viktor Milardić
(autor)
Katarina Musulin
(autor)