Earthing effects of bare conductor laid alongside underground power cables
Earthing effects of bare conductor laid alongside underground power cables // Proceedings of the Second IASTED International Conference Power and energy systems / Contaxis, George ; Antonidakis, Manolis (ur.).
Anaheim : Calgary : Zurich: ACTA Press, 2002. str. 612-616 (predavanje, međunarodna recenzija, cjeloviti rad (in extenso), znanstveni)
CROSBI ID: 121583 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
Earthing effects of bare conductor laid alongside underground power cables
Autori
Medić, Ivan ; Sarajčev, Ivan ; Majstrović, Matislav
Vrsta, podvrsta i kategorija rada
Radovi u zbornicima skupova, cjeloviti rad (in extenso), znanstveni
Izvornik
Proceedings of the Second IASTED International Conference Power and energy systems
/ Contaxis, George ; Antonidakis, Manolis - Anaheim : Calgary : Zurich : ACTA Press, 2002, 612-616
Skup
Power and energy systems
Mjesto i datum
Kreta, Grčka, 25.06.2002. - 28.06.2002
Vrsta sudjelovanja
Predavanje
Vrsta recenzije
Međunarodna recenzija
Ključne riječi
grounding; cable sheath; inductive coupling; earthing wire
Sažetak
An analytical method is presented to determine the line-to-ground fault current distribution and related voltages in the earthing system which consists of two substation earthings interconected by insulated metal sheaths of modern XLPE cables and one bare earthing wire laid in parallel in the same cable trench. The equations derived are based on the assumption of uniformly distributed conductance between the earthing wire and earth. The proposed method takes into account inductive coupling between cable sheaths and the earthing wire. The effects of connecting bare earthing wire parallel to insulated cable sheaths as well as that of their mutual inductance, are outlined. These effects may have significant influence on current and voltage distribution in earthing system. It is assumed that power cables operate in the network with non-directly earthed neutral point (e.g. 10-35 kV) so that relevant zero-sequence current is coming from another, directly earthed high voltage (h.v.) network.