Earth-fault detection and localization in isolated industrial MV network – comparison of directional overcurrent protection and signal injection method
Earth-fault detection and localization in isolated industrial MV network – comparison of directional overcurrent protection and signal injection method // International Conference on Power Systems Transients (IPST)
Belo Horizonte, Brazil, 2021. str. 1-7 (predavanje, međunarodna recenzija, cjeloviti rad (in extenso), znanstveni)
CROSBI ID: 1208477 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
Earth-fault detection and localization in isolated
industrial MV network – comparison of directional
overcurrent protection and signal injection method
Autori
Stipetić, Nina ; Filipović-Grčić, Božidar ; Uglešić, Ivo ; Xemard, Alain ; Andres, Naum
Vrsta, podvrsta i kategorija rada
Radovi u zbornicima skupova, cjeloviti rad (in extenso), znanstveni
Skup
International Conference on Power Systems Transients (IPST)
Mjesto i datum
Belo Horizonte, Brazil, 07.06.2021. - 10.06.2021
Vrsta sudjelovanja
Predavanje
Vrsta recenzije
Međunarodna recenzija
Ključne riječi
isolated network ; earth-fault ; directional earth-fault protection ; low-frequency signal injection
Sažetak
- Neutral earthing directly affects systems' behavior regarding the maximum level of earth- fault current and overvoltages. Isolated neutral is used where continuity of power supply is essential, which is often the case in industrial power utilities. Although the system can remain in service during a single-phase earth-fault, locating the fault should be done as quickly as possible, without disrupting the operation of the loads. Directional earth-fault protection (67N) can be used to indicate the faulty feeder. An alternative method is low-frequency (LF) current injection combined with sensors for detecting the injected signal, which is a known technique used in LV systems. In this paper, the application of 67N protection and the LF current injection method are tested on the same MV system with inaccessible neutral point. Inductive voltage transformers (IVTs) are used for signal injection. Both methods are discussed, and their limitations are compared based on simulation results obtained using the model of an isolated MV industrial plant. The model includes relay protection devices and IVTs for signal injection.