Pregled bibliografske jedinice broj: 1161704
Model of Static Var Compensator Connected to the Power Transmission Network for Electromagnetic Transient Studies
Model of Static Var Compensator Connected to the Power Transmission Network for Electromagnetic Transient Studies // SEERC 2021 - 3rd Conference of the South-East European Regional Council of CIGRE / Reich, Klemens (ur.).
Beč: CIGRÉ, 2021. str. 1-10 (predavanje, međunarodna recenzija, cjeloviti rad (in extenso), znanstveni)
CROSBI ID: 1161704 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
Model of Static Var Compensator Connected to the
Power Transmission Network for Electromagnetic
Transient Studies
Autori
Filipovic-Grcic, B. ; Damjanovic, I. ; Teklic, Lj. ; Lasic, M. ; Jurisic, B.
Vrsta, podvrsta i kategorija rada
Radovi u zbornicima skupova, cjeloviti rad (in extenso), znanstveni
Izvornik
SEERC 2021 - 3rd Conference of the South-East European Regional Council of CIGRE
/ Reich, Klemens - Beč : CIGRÉ, 2021, 1-10
Skup
The 3rd SEERC Conference 2021 (CIGRE SEERC)
Mjesto i datum
Beč, Austrija; online, 30.11.2021
Vrsta sudjelovanja
Predavanje
Vrsta recenzije
Međunarodna recenzija
Ključne riječi
Static var compensator (SVC), electromagnetic transients, thyristor-controlled reactors (TCR), harmonic filters.
Sažetak
Static var compensator (SVC) models for electromagnetic transient studies must accurately represent the SVC characteristics for steady state, dynamic and transient conditions. Studies in the specification development and design stages must evaluate the interaction between the SVC and the network for many different transient conditions. SVC considered in this paper consists of two thyristor-controlled reactor (TCR) branches. SVC model for simulation of electromagnetic transients was developed in EMTP-RV software. It includes detailed models of TCRs, harmonic filters, power transformer and control systems of SVC. Dynamic response of SVC to voltage changes at the connection point is investigated. The efficiency of the fifth and seventh harmonic filters for the different modes of SVC operation were analysed as well as the influence of SVC operation on the harmonics in the transmission network. Dynamic response of SVC is analysed during several electromagnetic transients such as SVC energization and fault application/clearance events in the surrounding transmission network.
Izvorni jezik
Engleski
Znanstvena područja
Elektrotehnika
POVEZANOST RADA
Ustanove:
KONČAR - Institut za elektrotehniku d.d.,
Fakultet elektrotehnike i računarstva, Zagreb
Profili:
Ivana Hrgović
(autor)
Božidar Filipović-Grčić
(autor)
Bruno Jurišić
(autor)
Mate Lasić
(autor)
Ljupko Teklić
(autor)