Pregled bibliografske jedinice broj: 1160991
Temperature rise of power transformers: Comments and proposals to IEC 60076-2:2011
Temperature rise of power transformers: Comments and proposals to IEC 60076-2:2011 // 3rd International Colloquium Transformer Research and Asset Management
Zagreb: CIGRÉ, 2014. str. 1-10 (predavanje, međunarodna recenzija, cjeloviti rad (in extenso), stručni)
CROSBI ID: 1160991 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
Temperature rise of power transformers: Comments and
proposals to IEC 60076-2:2011
Autori
Godec, Zdenko ; Kuprešanin, Vjenceslav
Vrsta, podvrsta i kategorija rada
Radovi u zbornicima skupova, cjeloviti rad (in extenso), stručni
Izvornik
3rd International Colloquium Transformer Research and Asset Management
/ - Zagreb : CIGRÉ, 2014, 1-10
Skup
3rd International Colloquium Transformer Research and Asset Management
Mjesto i datum
Split, Hrvatska, 15.10.2014. - 17.10.2014
Vrsta sudjelovanja
Predavanje
Vrsta recenzije
Međunarodna recenzija
Ključne riječi
Power transformers, temperature rise test, measurement uncertainty, decision-making
Sažetak
Two years ago, a new, third edition of IEC 60076-2 standard was published [1]. Over a period of two years, we have had the opportunity to evaluate this new standard in practice. In the paper, it is shown that the criterion for stagnation 1K/ h + 3h is not entirely satisfying. Better criterion is 1K/3h, or extrapolation to stagnation - as given in second edition of the standard. A formula for hot-spot determination is not complete and it is suggested how to improve it. In the new standard, three formulas for winding average temperature determination are given. Based on experiments, we conclude that the best formula is the simplest one, and two additional formulas are without any benefit. According to [1], paragraph 7.11, measurement uncertainty estimates of results should be given in test reports - but only as information. No procedure for measurement uncertainty estimation is given, and measurement uncertainty is not used in decision-making. Therefore, the third edition of the standard is uncompleted and not motivating in terms of efforts to increase the quality of the measurement results. In the paper, the procedure for measurement uncertainty estimation is proposed and suggestion is given for appropriate decision making.
Izvorni jezik
Engleski
Znanstvena područja
Elektrotehnika