Pregled bibliografske jedinice broj: 1157807
A contribution to more accurate determination of steady - state temperature rises in transformers by heat run
A contribution to more accurate determination of steady - state temperature rises in transformers by heat run // Končar journal, 1 (1988), 1; 6-8 (domaća recenzija, članak, znanstveni)
CROSBI ID: 1157807 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
A contribution to more accurate determination of
steady - state temperature rises in transformers
by heat run
Autori
Godec, Zdenko
Izvornik
Končar journal (0350-5537) 1
(1988), 1;
6-8
Vrsta, podvrsta i kategorija rada
Radovi u časopisima, članak, znanstveni
Ključne riječi
power transformers, heat run, temperature rise tests, determination of steady-state temperature rise, new method, measurements
Sažetak
A new criterion is proposed for the determination of the necessary duration of transformer temperature rise tests. The new criterion and the extrapolation of only those measured points that lie above 60% of the steady-state temperature rise ensure a higher accuracy of determination of steady-state oil and winding temperature rises, independently of the transformer thermal time constant.
Izvorni jezik
Engleski
Znanstvena područja
Elektrotehnika