Pregled bibliografske jedinice broj: 1148231
Consequences of energy efficiency measures implementation to buildings' electrical systems
Consequences of energy efficiency measures implementation to buildings' electrical systems // Tehnički vjesnik, 18 (2011), 1; 1-13 (međunarodna recenzija, članak, znanstveni)
CROSBI ID: 1148231 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
Consequences of energy efficiency measures implementation to buildings' electrical systems
Autori
Franković, Dubravko ; Pavković, Branimir ; Bupić, Matko
Izvornik
Tehnički vjesnik (1330-3651) 18
(2011), 1;
1-13
Vrsta, podvrsta i kategorija rada
Radovi u časopisima, članak, znanstveni
Ključne riječi
consequences ; energy efficiency measures ; harmonic load flow ; pumps ; refrigeration machines
Sažetak
Different consequences of energy efficiency measures implementation, in low voltage installations, have been presented and analyzed. Especially, impact of energy inefficient light sources replacement by efficient lamps, and addition of variables speed drives to existing induction machines have been examined. The mentioned impacts have been analyzed on a small low voltage radial distribution network by harmonic power flow calculations. Nonlinear loads were modeled upon laboratory measurements of different compact fluorescent lamps and variable speed drives and harmonic analysis of respective current-voltage waveforms. In addition, impact of variable speed control on refrigeration machines and pumps has been examined and the results presented.
Izvorni jezik
Engleski
Znanstvena područja
Elektrotehnika
POVEZANOST RADA
Ustanove:
Tehnički fakultet, Rijeka,
Sveučilište u Dubrovniku
Citiraj ovu publikaciju:
Časopis indeksira:
- Web of Science Core Collection (WoSCC)
- Science Citation Index Expanded (SCI-EXP)
- SCI-EXP, SSCI i/ili A&HCI
- Scopus