Pregled bibliografske jedinice broj: 113522
Electromagnetic Disturbances of the Secondary Circuits in Gas Insulated Substation due to Disconnector Switching
Electromagnetic Disturbances of the Secondary Circuits in Gas Insulated Substation due to Disconnector Switching // Conference Proceedings of International Conference on Power Systems Transients - IPST 2003 Hong Kong (New Orleans)
New Orleans (LA), Sjedinjene Američke Države, 2003. (predavanje, međunarodna recenzija, cjeloviti rad (in extenso), znanstveni)
CROSBI ID: 113522 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
Electromagnetic Disturbances of the Secondary Circuits in Gas Insulated Substation due to Disconnector Switching
Autori
Uglešić, Ivo ; Hutter, Sandra ; Milardić, Viktor ; Ivanković, Igor ; Filipović-Grčić Božidar
Vrsta, podvrsta i kategorija rada
Radovi u zbornicima skupova, cjeloviti rad (in extenso), znanstveni
Izvornik
Conference Proceedings of International Conference on Power Systems Transients - IPST 2003 Hong Kong (New Orleans)
/ - , 2003
Skup
International Conference on Power Systems Transients - IPST 2003 Hong Kong (New Orleans)
Mjesto i datum
New Orleans (LA), Sjedinjene Američke Države, 09.2003
Vrsta sudjelovanja
Predavanje
Vrsta recenzije
Međunarodna recenzija
Ključne riječi
electromagnetic compatibility (EMC); transient enclosure voltage (TEV); busbar protection; gas insulated switchgear (GIS)
Sažetak
The paper describes problems with electromagnetic compatibility (EMC) of the secondary equipment in the 123 kV gas insulated switchgear (GIS). The causes for malfunc-tioning of the busbar protection during disconnector switch-ing have been studied. Thorough measurements and computer simulations were conducted in order to determine magnitudes and frequencies of the transient voltages and currents in the secondary circuits. Although measured secondary transients had lower magnitudes than allowed, they caused malfunction-ing of the secondary equipment, e.g. busbar protection. Con-tinuous monitoring of the HV equipment's influence on the secondary equipment and implementation of some precau-tionary protection measures are recommended.