Naslov
Electromagnetic Disturbances of the Secondary Circuits in Gas Insulated Substation due to Disconnector Switching

Autori
Uglešić, Ivo ; Hutter, Sandra ; Milardić, Viktor ; Ivanković, Igor ; Filipović-Grčić Božidar

Vrsta, podvrsta i kategorija rada
Radovi u zbornicima skupova, cjeloviti rad (in extenso), znanstveni

Izvornik
Conference Proceedings of International Conference on Power Systems Transients - IPST 2003 Hong Kong (New Orleans) / - , 2003

Skup
International Conference on Power Systems Transients - IPST 2003 Hong Kong (New Orleans)

Mjesto i datum
New Orleans (LA), Sjedinjene Američke Države, 09.2003

Vrsta sudjelovanja
Predavanje

Vrsta recenzije
Međunarodna recenzija

Ključne riječi
electromagnetic compatibility (EMC); transient enclosure voltage (TEV); busbar protection; gas insulated switchgear (GIS)

Sažetak
The paper describes problems with electromagnetic compatibility (EMC) of the secondary equipment in the 123 kV gas insulated switchgear (GIS). The causes for malfunc-tioning of the busbar protection during disconnector switch-ing have been studied. Thorough measurements and computer simulations were conducted in order to determine magnitudes and frequencies of the transient voltages and currents in the secondary circuits. Although measured secondary transients had lower magnitudes than allowed, they caused malfunction-ing of the secondary equipment, e.g. busbar protection. Con-tinuous monitoring of the HV equipment's influence on the secondary equipment and implementation of some precau-tionary protection measures are recommended.

Izvorni jezik
Engleski

Znanstvena područja
Elektrotehnika



POVEZANOST RADA


Projekti:
0036008

Ustanove:
Fakultet elektrotehnike i računarstva, Zagreb


Citiraj ovu publikaciju:

Uglešić, Ivo; Hutter, Sandra; Milardić, Viktor; Ivanković, Igor; Filipović-Grčić Božidar
Electromagnetic Disturbances of the Secondary Circuits in Gas Insulated Substation due to Disconnector Switching // Conference Proceedings of International Conference on Power Systems Transients - IPST 2003 Hong Kong (New Orleans)
New Orleans (LA), Sjedinjene Američke Države, 2003. (predavanje, međunarodna recenzija, cjeloviti rad (in extenso), znanstveni)
Uglešić, I., Hutter, S., Milardić, V., Ivanković, I. & Filipović-Grčić Božidar (2003) Electromagnetic Disturbances of the Secondary Circuits in Gas Insulated Substation due to Disconnector Switching. U: Conference Proceedings of International Conference on Power Systems Transients - IPST 2003 Hong Kong (New Orleans).
@article{article, author = {Ugle\v{s}i\'{c}, Ivo and Hutter, Sandra and Milardi\'{c}, Viktor and Ivankovi\'{c}, Igor}, year = {2003}, keywords = {electromagnetic compatibility (EMC), transient enclosure voltage (TEV), busbar protection, gas insulated switchgear (GIS)}, title = {Electromagnetic Disturbances of the Secondary Circuits in Gas Insulated Substation due to Disconnector Switching}, keyword = {electromagnetic compatibility (EMC), transient enclosure voltage (TEV), busbar protection, gas insulated switchgear (GIS)}, publisherplace = {New Orleans (LA), Sjedinjene Ameri\v{c}ke Dr\v{z}ave} }
@article{article, author = {Ugle\v{s}i\'{c}, Ivo and Hutter, Sandra and Milardi\'{c}, Viktor and Ivankovi\'{c}, Igor}, year = {2003}, keywords = {electromagnetic compatibility (EMC), transient enclosure voltage (TEV), busbar protection, gas insulated switchgear (GIS)}, title = {Electromagnetic Disturbances of the Secondary Circuits in Gas Insulated Substation due to Disconnector Switching}, keyword = {electromagnetic compatibility (EMC), transient enclosure voltage (TEV), busbar protection, gas insulated switchgear (GIS)}, publisherplace = {New Orleans (LA), Sjedinjene Ameri\v{c}ke Dr\v{z}ave} }




Contrast
Increase Font
Decrease Font
Dyslexic Font