Pregled bibliografske jedinice broj: 1097466
A Laboratory Setup for Testing Frequency Estimation Algorithms Implemented on Real-Time Target
A Laboratory Setup for Testing Frequency Estimation Algorithms Implemented on Real-Time Target // 2020 3rd International Colloquium on Intelligent Grid Metrology (SMAGRIMET) / Ivšić, Branimir ; Petrović, Goran ; Dadić, Martin (ur.).
Zagreb: Fakultet elektrotehnike i računarstva Sveučilišta u Zagrebu, 2020. str. 98-103 doi:10.23919/smagrimet48809.2020.9264023 (predavanje, međunarodna recenzija, cjeloviti rad (in extenso), znanstveni)
CROSBI ID: 1097466 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
A Laboratory Setup for Testing Frequency Estimation Algorithms Implemented on Real-Time Target
Autori
Kunac, Antonio ; Petrovic, Goran ; Despalatovic, Marin ; Jurcevic, Marko
Vrsta, podvrsta i kategorija rada
Radovi u zbornicima skupova, cjeloviti rad (in extenso), znanstveni
Izvornik
2020 3rd International Colloquium on Intelligent Grid Metrology (SMAGRIMET)
/ Ivšić, Branimir ; Petrović, Goran ; Dadić, Martin - Zagreb : Fakultet elektrotehnike i računarstva Sveučilišta u Zagrebu, 2020, 98-103
ISBN
978-953-184-265-5
Skup
3rd International Colloquium on Intelligent Grid Metrology (SMAGRIMET 2020)
Mjesto i datum
Hrvatska; online, 20.10.2020. - 23.10.2020
Vrsta sudjelovanja
Predavanje
Vrsta recenzije
Međunarodna recenzija
Ključne riječi
Real-time systems, Power system harmonics, Calibration, Kalman filters, Frequency estimation
Sažetak
In this paper a low-budget single-phase voltagewaveform simulator based on the NI PCI-6071E DAQ card anddesktop PC with real-time Phar Lap operating system has beenpresented. Program for generating waveforms in accordanceto the IEC standard 61000-4-13, with harmonics of variablefrequency, amplitude and phase, has been implemented in theLabVIEW RT environment. Calibration of DAQ card internalclock has been performed to increase the accuracy of the gener-ated voltage waveform frequency. In order to achieve consistentsystem operation, DAQ card internal temperature sensor hasbeen used to compensate clock frequency drift caused by localambient temperature variations. For verification purposes, oneof algorithms for the frequency estimation based on the linearKalman filter has been deployed to target PC. Experimentalresults in steady-state and dynamics have also been presented.The estimated frequency of the generated signal matches verywell with the values obtained by the digital multimeter used forcalibration procedure.
Izvorni jezik
Engleski
Znanstvena područja
Elektrotehnika
POVEZANOST RADA
Projekti:
IP-2019-04-7292 - Simulator poremećaja u elektroenergetskom sustavu i kalibrator nesinusnih napona i struja (SIMPES) (Petrović, Goran, HRZZ - 2019-04) ( CroRIS)
Ustanove:
Fakultet elektrotehnike, strojarstva i brodogradnje, Split,
Fakultet elektrotehnike i računarstva, Zagreb
Profili:
Antonijo Kunac
(autor)
Marko Jurčević
(autor)
Marin Despalatović
(autor)
Goran Petrović
(autor)