Pregled bibliografske jedinice broj: 1082019
Core-type transformer short-circuit voltage calculation using conformal mapping
Core-type transformer short-circuit voltage calculation using conformal mapping // IET electric power applications, 14 (2020), 12; 2422-2430 doi:10.1049/iet-epa.2020.0351 (međunarodna recenzija, članak, znanstveni)
CROSBI ID: 1082019 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
Core-type transformer short-circuit voltage
calculation using conformal mapping
Autori
Jurković, Mario ; Žarko, Damir
Izvornik
IET electric power applications (1751-8660) 14
(2020), 12;
2422-2430
Vrsta, podvrsta i kategorija rada
Radovi u časopisima, članak, znanstveni
Ključne riječi
Short-circuit voltage, conformal mapping, Schwarz-Christoffel transformation
Sažetak
This study describes a method for calculation of transformer short-circuit voltage using conformal mappings, which map the transformer longitudinal and transverse cross-section geometry to a unit disk where an analytical solution for magnetic flux density is obtained and then transformed back to the original domain. The short-circuit voltage is calculated by the integration of the magnetic energy of the leakage field in the windings and the space around windings, excluding the core. This method takes into account windings of different height, the fringing effect at the ends of the windings and any relative position of windings located on the same or different limbs. Also, it is possible to calculate the short-circuit voltage for multiple windings.
Izvorni jezik
Engleski
Znanstvena područja
Elektrotehnika
POVEZANOST RADA
Ustanove:
Fakultet elektrotehnike i računarstva, Zagreb
Citiraj ovu publikaciju:
Časopis indeksira:
- Current Contents Connect (CCC)
- Web of Science Core Collection (WoSCC)
- Science Citation Index Expanded (SCI-EXP)
- SCI-EXP, SSCI i/ili A&HCI
- Scopus