Pregled bibliografske jedinice broj: 1025175
Operating experience with a transient overvoltages monitoring system installed on power transformers and shunt reactors
Operating experience with a transient overvoltages monitoring system installed on power transformers and shunt reactors // 1st Conference of Nacional Committee CIGRE Kosovo
Priština, kosovo, 2019. str. 1-10 (predavanje, međunarodna recenzija, cjeloviti rad (in extenso), znanstveni)
CROSBI ID: 1025175 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
Operating experience with a transient
overvoltages monitoring system installed on
power transformers and shunt reactors
Autori
Keitoue, Samir ; Filipović-Grčić, Božidar
Vrsta, podvrsta i kategorija rada
Radovi u zbornicima skupova, cjeloviti rad (in extenso), znanstveni
Izvornik
1st Conference of Nacional Committee CIGRE Kosovo
/ - , 2019, 1-10
Skup
1st Conference of Nacional Committee CIGRE Kosovo
Mjesto i datum
Priština, kosovo, 06.11.2019. - 08.11.2019
Vrsta sudjelovanja
Predavanje
Vrsta recenzije
Međunarodna recenzija
Ključne riječi
Transient overvoltage monitoring system ; Lightning and switching overvoltages ; Power transformers ; Shunt reactors
Sažetak
Transient overvoltages generated by lightning strikes or switching operations represent a significant risk to insulation system of power transformers and shunt reactors. Since the exposure of equipment to overvoltages during operation and the overvoltage amplitudes are usually unknow, an on-line overvoltage transient recorder is used with the ability to sample, analyse and store transients at transformer terminals in real-time. In this paper, transient overvoltage monitoring system is presented. Overvoltages are measured on the outside measurement terminal of the shunt reactor and transformer bushing. Operating experience regarding the application of monitoring systems in field is described including different cases of lightning and switching overvoltages. Lightning overvoltages recorded by monitoring system are correlated with data from the lightning location system (LLS). Switching overvoltages recorded on the shunt reactor are compared with numerical simulations in EMTP-RV software. Collected data about overvoltage stresses can be used as the basis for the assessment of the transformer and shunt reactor insulation condition and estimation of health index.
Izvorni jezik
Engleski
Znanstvena područja
Elektrotehnika
POVEZANOST RADA
Ustanove:
KONČAR - Institut za elektrotehniku d.d.,
Fakultet elektrotehnike i računarstva, Zagreb