Pregled bibliografske jedinice broj: 1022800
Evaluating the overvoltage performance of an overhead line taking into account the frequency-dependence of its tower’s grounding electrodes with high soil resistivity
Evaluating the overvoltage performance of an overhead line taking into account the frequency-dependence of its tower’s grounding electrodes with high soil resistivity // International journal of electrical power & energy systems, 116 (2020), 105547, 6 (međunarodna recenzija, članak, znanstveni)
CROSBI ID: 1022800 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
Evaluating the overvoltage performance of an overhead line taking into account the frequency-dependence of its tower’s grounding electrodes with high soil resistivity
Autori
Piliškić, Silvia ; Uglešić, Ivo ; Jurišić, Bruno
Izvornik
International journal of electrical power & energy systems (0142-0615) 116
(2020);
105547, 6
Vrsta, podvrsta i kategorija rada
Radovi u časopisima, članak, znanstveni
Ključne riječi
Tower grounding impedance ; Frequency dependence ; Lightning ; Overvoltage performance ; Line surge arrester
Sažetak
The paper demonstrates the importance of taking the frequency-dependence of the tower grounding impedance into account when studying the lightning performance of an overhead line located in an area with high soil resistivity. Towers’ impulse grounding impedance measurements and their rational approximations are used to construct a wideband model of the towers’ grounding electrodes in an EMTP-type software program. In order to examine the impact of tower grounding impedances, simulations of lightning strokes to the overhead line tower were performed using an EMTP-type tool in the following three different cases: constant grounding impedance of the tower hit by a lightning stroke, frequency-dependent tower grounding impedance and frequency-dependent tower grounding impedance for the tower equipped with a Line Surge Arrester (LSA) installed at the lowest phase. The simulations have shown the influence of the frequency-dependence of the tower grounding impedance on the level of the build-up voltage across the tower’s insulator string and consequently on the flashover occurrence in the observed configuration with a high soil resistivity.
Izvorni jezik
Engleski
Znanstvena područja
Elektrotehnika
POVEZANOST RADA
Ustanove:
KONČAR - Institut za elektrotehniku d.d.,
Fakultet elektrotehnike i računarstva, Zagreb
Citiraj ovu publikaciju:
Časopis indeksira:
- Current Contents Connect (CCC)
- Web of Science Core Collection (WoSCC)
- Science Citation Index Expanded (SCI-EXP)
- SCI-EXP, SSCI i/ili A&HCI
- Scopus