Pregled bibliografske jedinice broj: 906369
Analysis of the impact of different operating conditions on the performance of a reversible heat pump with domestic hot water production
Analysis of the impact of different operating conditions on the performance of a reversible heat pump with domestic hot water production // International journal of refrigeration, 86 (2018), 282-291 doi:10.1016/j.ijrefrig.2017.11.005 (međunarodna recenzija, članak, znanstveni)
CROSBI ID: 906369 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
Analysis of the impact of different operating conditions on the performance of a reversible heat pump with domestic hot water production
Autori
Janković, Zvonimir ; Sierea Atienza, Jaime ; Cerdeira Perez, Fernando ; Pavković, Branimir
Izvornik
International journal of refrigeration (0140-7007) 86
(2018);
282-291
Vrsta, podvrsta i kategorija rada
Radovi u časopisima, članak, znanstveni
Ključne riječi
Heat pump ; Mathematical model ; Desuperheater ; Liquid-vapor heat exchanger ; Experimental results
Sažetak
This paper presents the mathematical modelling of a liquid-to-water heat pump with scroll compressor, brazed plate heat exchangers, additionally built-in liquid-vapor heat exchanger (LVHX) and a desuperheater for domestic hot water (DHW) production. The refrigerant is the zeotropic mixture R407C and the liquid used in the outdoor loop is a propylene-glycol water mixture. Developed mathematical model is validated on experimental data and used as a tool for the heat pump analysis. Simulation results are obtained for the effect of the degree of superheat at the evaporator outlet, the subcooling degree at the condenser outlet, the effect of using or not the LVHX and the effect of using or not the desuperheater for DHW for typical operating conditions of liquid-to-water heat pumps (EN- 14511-2, 2011) in the cooling and heating modes (low and medium temperature applications). Results show that the effect of the degree of superheat or the decision on the suitability of using or not a LVHX may be different for heat pumps that include or not a desuperheater for DHW. In particular, if DHW is a priority, the use of a LVHX is recommended because it leads to higher COP (or EER) values as well as to higher DHW heating powers.
Izvorni jezik
Engleski
Znanstvena područja
Strojarstvo
POVEZANOST RADA
Ustanove:
Tehnički fakultet, Rijeka,
Strojarski fakultet, Slavonski Brod
Citiraj ovu publikaciju:
Časopis indeksira:
- Current Contents Connect (CCC)
- Web of Science Core Collection (WoSCC)
- Science Citation Index Expanded (SCI-EXP)
- SCI-EXP, SSCI i/ili A&HCI
- Scopus