Pregled bibliografske jedinice broj: 889542
Calculation of internal overvoltages using a wide band transformer model based on limited information about transformer design
Calculation of internal overvoltages using a wide band transformer model based on limited information about transformer design // 4th International Colloquium "Transformer Research and Asset Management”
Pula, 2017. (predavanje, međunarodna recenzija, cjeloviti rad (in extenso), znanstveni)
CROSBI ID: 889542 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
Calculation of internal overvoltages using a wide band transformer model based on limited information about transformer design
Autori
Jurišić, Bruno ; Poujade, Paul ; Uglešić, Ivo ; Xemard, Alain ; Paladian, Francoise
Vrsta, podvrsta i kategorija rada
Radovi u zbornicima skupova, cjeloviti rad (in extenso), znanstveni
Izvornik
4th International Colloquium "Transformer Research and Asset Management”
/ - Pula, 2017
Skup
4th International Colloquium "Transformer Research and Asset Management”
Mjesto i datum
Pula, Hrvatska, 10.05.2017. - 12.05.2017
Vrsta sudjelovanja
Predavanje
Vrsta recenzije
Međunarodna recenzija
Ključne riječi
Transformer modelling ; Grey Box ; Complex permeability ; ElectroMagnetic Transients Programme ; Internal overvoltages
Sažetak
Specific insulation coordination studies might require an accurate modeling of power transformers. This is the case for instance when transfers of fast front overvoltages from the high voltage side to the low voltage side of a transformer are involved. Modeling accurately the transformer’s electromagnetic behavior for the frequency range of fast front overvoltages requires special care. There are numerous existing transformer models which are intended to model the wide band transformer’s behavior. However, many of them are too complex or require confidential information about the transformer design. This makes them not suitable for power engineering applications. In this paper a wide band transformer model based on limited information about the transformer design and compatible with an electromagnetic transients program is presented. Then, its application on calculating internal overvoltages distribution along transformer windings, taking into account different conditions on the outer transformer terminals, is shown for lightning impulse.
Izvorni jezik
Engleski
Znanstvena područja
Elektrotehnika
POVEZANOST RADA
Projekti:
HRZZ-IP-2013-11-9299 - Razvoj naprednih visokonaponskih sustava primjenom novih informacijskih i komunikacijskih tehnologija (DAHVAT) (Uglešić, Ivo, HRZZ ) ( CroRIS)
Ustanove:
Fakultet elektrotehnike i računarstva, Zagreb