High frequency transformer model derived from limited information about the transformer geometry


Jurišić, Bruno; Uglešić, Ivo; Xemard, Alain; Paladian, Francoise
High frequency transformer model derived from limited information about the transformer geometry // International journal of electrical power & energy systems, 94 (2018), 300-310 doi:10.1016/j.ijepes.2017.07.017 (međunarodna recenzija, članak, znanstveni)


CROSBI ID: 888928 Za ispravke kontaktirajte CROSBI podršku putem web obrasca

Naslov
High frequency transformer model derived from limited information about the transformer geometry

Autori
Jurišić, Bruno ; Uglešić, Ivo ; Xemard, Alain ; Paladian, Francoise

Izvornik
International journal of electrical power & energy systems (0142-0615) 94 (2018); 300-310

Vrsta, podvrsta i kategorija rada
Radovi u časopisima, članak, znanstveni

Ključne riječi
Grey Box ; Complex permeability ; Fitting ; Passivity enforcement ; Transformer modelling

Sažetak
To represent transformer behaviour during a transient state which includes high frequencies, it is necessary to consider the resonances which occur inside the transformer. One strategy is to deduce the transformer model from the measurements of the transformer’s frequency response, another one is to construct the model based on a careful representation of the inside of the apparatus. In the paper a model is presented which is compatible with EMTP-type software programs based on a finite element method (FEM) calculations and the complex permeability approximation. The model can be classified as a Grey Box transformer model, according to the terminology of the CIGRE. The model’s frequency dependent parameters are derived from limited information about the transformer geometry. State space equations are used to input the model into an electromagnetic transient calculation software program. This approach requires specific mathematical treatments to avoid stability issues during simulations. The model is validated for lightning impulse studies using the field test measurements of over-voltages that had occurred at the external transformer’s terminals.

Izvorni jezik
Engleski

Znanstvena područja
Elektrotehnika



POVEZANOST RADA


Projekti:
HRZZ-IP-2013-11-9299 - Razvoj naprednih visokonaponskih sustava primjenom novih informacijskih i komunikacijskih tehnologija (DAHVAT) (Uglešić, Ivo, HRZZ ) ( CroRIS)

Ustanove:
Fakultet elektrotehnike i računarstva, Zagreb

Profili:

Avatar Url Bruno Jurišić (autor)

Avatar Url Ivo Uglešić (autor)

Poveznice na cjeloviti tekst rada:

doi doi.org www.sciencedirect.com www.sciencedirect.com

Citiraj ovu publikaciju:

Jurišić, Bruno; Uglešić, Ivo; Xemard, Alain; Paladian, Francoise
High frequency transformer model derived from limited information about the transformer geometry // International journal of electrical power & energy systems, 94 (2018), 300-310 doi:10.1016/j.ijepes.2017.07.017 (međunarodna recenzija, članak, znanstveni)
Jurišić, B., Uglešić, I., Xemard, A. & Paladian, F. (2018) High frequency transformer model derived from limited information about the transformer geometry. International journal of electrical power & energy systems, 94, 300-310 doi:10.1016/j.ijepes.2017.07.017.
@article{article, author = {Juri\v{s}i\'{c}, Bruno and Ugle\v{s}i\'{c}, Ivo and Xemard, Alain and Paladian, Francoise}, year = {2018}, pages = {300-310}, DOI = {10.1016/j.ijepes.2017.07.017}, keywords = {Grey Box, Complex permeability, Fitting, Passivity enforcement, Transformer modelling}, journal = {International journal of electrical power and energy systems}, doi = {10.1016/j.ijepes.2017.07.017}, volume = {94}, issn = {0142-0615}, title = {High frequency transformer model derived from limited information about the transformer geometry}, keyword = {Grey Box, Complex permeability, Fitting, Passivity enforcement, Transformer modelling} }
@article{article, author = {Juri\v{s}i\'{c}, Bruno and Ugle\v{s}i\'{c}, Ivo and Xemard, Alain and Paladian, Francoise}, year = {2018}, pages = {300-310}, DOI = {10.1016/j.ijepes.2017.07.017}, keywords = {Grey Box, Complex permeability, Fitting, Passivity enforcement, Transformer modelling}, journal = {International journal of electrical power and energy systems}, doi = {10.1016/j.ijepes.2017.07.017}, volume = {94}, issn = {0142-0615}, title = {High frequency transformer model derived from limited information about the transformer geometry}, keyword = {Grey Box, Complex permeability, Fitting, Passivity enforcement, Transformer modelling} }