Pregled bibliografske jedinice broj: 76715
Some Aspects of Stray Losses in Large Power Trasnformers
Some Aspects of Stray Losses in Large Power Trasnformers // Proceedings of the 3^rd Japanese-Bulgarian-Macedonian Joint Seminar on Applied Electromagnetics / Yamashita, A. ; Marinova, I. ; Cingoski, V. (ur.).
Ohrid, Sjeverna Makedonija, 2000. str. 238-243 (predavanje, međunarodna recenzija, cjeloviti rad (in extenso), znanstveni)
CROSBI ID: 76715 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
Some Aspects of Stray Losses in Large Power Trasnformers
Autori
Valković, Zvonimir
Vrsta, podvrsta i kategorija rada
Radovi u zbornicima skupova, cjeloviti rad (in extenso), znanstveni
Izvornik
Proceedings of the 3^rd Japanese-Bulgarian-Macedonian Joint Seminar on Applied Electromagnetics
/ Yamashita, A. ; Marinova, I. ; Cingoski, V. - , 2000, 238-243
Skup
3^rd Japanese-Bulgarian-Macedonian Joint Seminar on Applied Electromagnetics
Mjesto i datum
Ohrid, Sjeverna Makedonija, 15.09.2000. - 17.09.2000
Vrsta sudjelovanja
Predavanje
Vrsta recenzije
Međunarodna recenzija
Ključne riječi
transformer; stray losses; high currents
Sažetak
The paper presents some results of the investigation of stray losses in power transformers that are caused by high-current loops. The investigation was focused on: a) additional losses in tank cover around high-current bushings and the way of their reduction, b) extra leakage flux and additional losses due to high-current delta-connections. The insertion of nonmagnetic gaps between the phase bushings reduces the extra cover losses more than three times. A nonmagnetic plate around the high-current bushings reduces these extra losses practically to zero. The extra losses due to the high-current delta-connections could be significant for the transformer loss level. These extra losses could be controlled (reduced) by the design layout of the delta-connections.
Izvorni jezik
Engleski
POVEZANOST RADA
Ustanove:
KONČAR - Institut za elektrotehniku d.d.
Profili:
Zvonimir Valković
(autor)