Additional Losses in Overlapping Area of Transformer Core
Additional Losses in Overlapping Area of Transformer Core // Compel, 13 (1994), 1; 101-104 (međunarodna recenzija, članak, znanstveni)
CROSBI ID: 76396 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
Additional Losses in Overlapping Area of Transformer Core
Autori
Rezić, Ante ; Valković, Zvonimir
Izvornik
Compel (0332-1649) 13
(1994), 1;
101-104
Vrsta, podvrsta i kategorija rada
Radovi u časopisima, članak, znanstveni
Ključne riječi
transformer core; overlap; magnetic characteristics; experiments; numerical calculation
Sažetak
The influence of overlap length and overlapping design on core loss and magnetizing current of single-phase two-leg transformer core has been investigated. The investigation was performed experimentally, on scaled models, and numerically, using 2D finite element method. Two types of overlapping, mitred and staggered one, were investigated. It has been observed that the influence of overlap length on core magnetic characteristics is much higher in the case of the mitred overlap than that of the staggered one. This difference has been explained by the reduction of core cross section due to triangle cutout in the mitred overlap.