Pregled bibliografske jedinice broj: 706972
Thermal Properties of Synthetic Ester-based Transformer Oil During Ageing in Laboratory Conditions
Thermal Properties of Synthetic Ester-based Transformer Oil During Ageing in Laboratory Conditions // ICDL 2014: 18th IEEE International Conference on Dielectric Liquids, Bled, Slovenia, 30.06.-3.07.2014.
Bled: Institute of Electrical and Electronics Engineers (IEEE), 2014. str. 1-4 (predavanje, međunarodna recenzija, cjeloviti rad (in extenso), znanstveni)
CROSBI ID: 706972 Za ispravke kontaktirajte CROSBI podršku putem web obrasca
Naslov
Thermal Properties of Synthetic Ester-based Transformer Oil During Ageing in Laboratory Conditions
Autori
Haramija, Veronika ; Vrsaljko, Dijana ; Đurina, Vedran ; Vrsaljko, Domagoj
Vrsta, podvrsta i kategorija rada
Radovi u zbornicima skupova, cjeloviti rad (in extenso), znanstveni
Izvornik
ICDL 2014: 18th IEEE International Conference on Dielectric Liquids, Bled, Slovenia, 30.06.-3.07.2014.
/ - Bled : Institute of Electrical and Electronics Engineers (IEEE), 2014, 1-4
ISBN
978-1-4799-2064-8
Skup
ICDL 2014: 18th IEEE International Conference on Dielectric Liquids, Bled, Slovenia, 30.06.-3.07.2014.
Mjesto i datum
Bled, Slovenija, Bled, Slovenia
Vrsta sudjelovanja
Predavanje
Vrsta recenzije
Međunarodna recenzija
Ključne riječi
transformer oil ; synthetic ester ; ageing ; thermal
Sažetak
Synthetic esters are interesting as transformer insulating liquids for use in densely populated and environmentally sensitive areas because of high flashpoint, good biodegradability, low toxicity, good electrical and thermal properties, resistance to electrical discharges and compatibility with materials in transformers. Monitoring of liquid insulation is a convenient method for assessing general condition of the transformer. Since synthetic esters have only recently been put into use in power transformers, there is still not enough data on change of their properties during exploitation for transformer condition assessment. Monitoring changes of properties in laboratory ageing conditions, as well as the determination of characteristic degradation products will contribute to a better understanding of the insulating liquid and to the assessment of its functionality. In this paper, changes of physico-chemical properties of synthetic ester-based transformer oil in laboratory ageing conditions were investigated. The oil was submitted to 120 °C and 150 °C at different time intervals. After the exposure to high temperature, differential scanning calorimetry (DSC) and thermogravimetric analysis (TGA) were performed. DSC was performed for the purpose of gathering qualitative and quantitative data about physical and chemical processes that include endothermic and exothermic effects and heat capacity change. Heat capacity is highly affected by viscosity, so temperature dependence of viscosity as well as viscosity change during ageing was monitored. TGA was performed for the purpose of material characterization and gathering of information about thermal stability of oil. The investigation contributes to better understanding of thermal ageing kinetics of environmentally friendly synthetic ester-based insulating liquid.
Izvorni jezik
Engleski
Znanstvena područja
Elektrotehnika, Kemijsko inženjerstvo
POVEZANOST RADA
Ustanove:
KONČAR - Institut za elektrotehniku d.d.,
Fakultet kemijskog inženjerstva i tehnologije, Zagreb